Features:<br />
• Electronically<br />
Commutated (<strong>EC</strong>)<br />
fan motor<br />
• Specific <strong>Fan</strong> Power<br />
of 0.16 to 0.34 at<br />
NR35<br />
• Insignificant<br />
fan heat gain<br />
• Designed to operate<br />
below NR35 at<br />
External Static<br />
Pressures of up to<br />
50Pa<br />
• Variable speed<br />
<strong>Fan</strong> adjustment<br />
• Ceiling and<br />
Underfloor<br />
installation<br />
• Low surface<br />
temperature on<br />
electric element<br />
• Low Maintenance<br />
<strong>Highline</strong> <strong>260i</strong> <strong>EC</strong> <strong>Waterside</strong> <strong>Fan</strong> <strong>Coil</strong> <strong>Unit</strong>
<strong>Highline</strong> <strong>260i</strong> <strong>EC</strong> <strong>Waterside</strong> <strong>Fan</strong> <strong>Coil</strong> <strong>Unit</strong><br />
<strong>Fan</strong> <strong>Coil</strong> <strong>Unit</strong><br />
The most popular waterside control fan<br />
coil unit in the UK for the past 15<br />
years, now available with <strong>EC</strong> fans<br />
having low Specific <strong>Fan</strong> Powers.<br />
Initially designed to be fitted into a<br />
ceiling void, the flexibility also allows<br />
the unit to be installed underfloor.<br />
Furthermore an alternative to the<br />
standard design is the <strong>Highline</strong> 260d,<br />
which incorporates a detachable<br />
discharge plenum and enables a more<br />
flexible discharge arrangement.<br />
Chassis<br />
<strong>Unit</strong>s are manufactured from 1.0 -<br />
1.6mm hot dipped galvanised steel and<br />
are constructed without the use of self<br />
tapping screws. All thermal and<br />
acoustic lining is CFC and HCFC free<br />
and class ‘O’ fire rated. All bearings<br />
and moving surfaces will operate<br />
without requiring further lubrication.<br />
All electrical components and electrical<br />
wiring comply with the current edition<br />
of the I.E.E. regulations. Each unit is<br />
factory tested to ensure that it will<br />
continue to meet its specified<br />
performance with the minimum of<br />
maintenance, throughout its life.<br />
<strong>Fan</strong>s<br />
The fans are of the double inlet, double<br />
width centrifugal type. The scrolls are<br />
manufactured from galvanised mild<br />
steel, complete with forward curved<br />
aluminium or galvanised steel bladed<br />
impellers. All fan and motor assemblies<br />
are statically and dynamically balanced<br />
to prevent the transmission of vibration<br />
to the fan coil unit casing. Each fan<br />
and motor assembly has thermal<br />
overload protection fitted, via<br />
imbedded thermistors or the<br />
commutation electronics. The motors<br />
comply to BS 5000-11 and BS EN<br />
60034. The motor frame is totally<br />
enclosed and fitted with maintenance<br />
free sealed for life ball bearings.<br />
Motors are insulated to BS 2757 class<br />
B (minimum) and tested to BS EN<br />
61000-3-2 for Harmonic Distortion<br />
and BS EN 61000-3-3 for Flicker.<br />
Heat Exchangers <strong>Coil</strong>s are<br />
manufactured from 0.35 mm thick<br />
solid drawn copper tubes, mechanically<br />
expanded into accurately pre-formed<br />
collars in rippled aluminium fins. The<br />
coils are arranged for single or multicircuit<br />
operation via headers. Each<br />
coil is fitted with a manual air vent and<br />
drain point. All coils are factory tested<br />
to a minimum of 35 bar and are<br />
suitable for operating pressures of up to<br />
12 bar static head. <strong>Coil</strong>s are fitted<br />
with 15 mm o/d plain copper tails.<br />
Condensate Drip Tray<br />
The condensate drip tray is manufactured<br />
from hot dipped galvanised steel, welded<br />
at each corner. The tray is then degreased<br />
before anti-condensation insulation is<br />
applied to all internal and external<br />
surfaces. The tray is fitted with 15 mm o/<br />
d plain brass connection (22 mm o/d<br />
optional). The tray has a built in gradient<br />
to ensure correct drainage of condensate.<br />
Temperature Controls<br />
(WATERSIDE)<br />
Temperature control shall be by<br />
modulation of the control valves<br />
allowing either chilled or heated water<br />
to flow through the appropriate coil.<br />
Air Filter Options<br />
• Mesh Filter - The filter is<br />
permanent and is manufactured<br />
from a fine woven mesh of<br />
galvanised steel wire, welded to a<br />
rigid galvanised steel frame. It can<br />
be vacuum cleaned in-situ, or<br />
periodically removed for washing<br />
when necessary<br />
• Media type filter - Filters are EU2<br />
to Eurovent 4/5 and manufactured<br />
from a synthetic media secured to a<br />
wire metal frame and fitted<br />
with<br />
handles for<br />
ease of cleaning and<br />
replacement.<br />
Discharge/ Inlet Plenum<br />
The discharge and inlet plenums are<br />
attenuated and thermally lined with a<br />
CFC and HCFC free class ‘O’ fire<br />
retardant non-migratory foam, which<br />
is both vermin and rot proof. The<br />
density of the foam is 11 kg/m³<br />
thereby helping to reduce the total<br />
weight of the fan coil unit.<br />
Electric Heat Element (if required)<br />
The element is manufactured from<br />
stainless steel sheath with spiral<br />
wound stainless steel fins to minimise<br />
surface temperature. It is located<br />
upstream of the fan(s) to evenly<br />
distribute the heat to the final<br />
discharge spigots. Each unit shall<br />
incorporate a manual reset high<br />
temperature cut-out and a Pressure<br />
Differential Switch or Current Switch,<br />
wired to prevent operation in the<br />
event of a fan failure.
THERMAL<br />
PERFORMANCE<br />
EL<strong>EC</strong>TRIC DATA/<br />
FAN PERFORMANCE<br />
Model & Size<br />
Air Vol. l/s<br />
Speed<br />
Sens. Duty<br />
Watts<br />
Total Duty<br />
Watts<br />
CHW Flow<br />
Rate l/s<br />
Hyd. Res<br />
kPa<br />
Heat Duty<br />
Watts<br />
LPHW<br />
Flow Rate<br />
l/s<br />
Hyd. Res.<br />
kPa<br />
Running<br />
Current (A)<br />
Power<br />
Absorbed (W)<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH6CH<br />
Specific <strong>Fan</strong><br />
Power (SFP)<br />
W/I/s<br />
109 Extra low 1494 1895 0.075 3.63 815 0.018 0.28 0.17 23 0.21<br />
122 Low 1667 2112 0.084 4.42 898 0.02 0.34 0.23 31 0.25<br />
143 Low + 1911 2392 0.095 5.55 984 0.022 0.4 0.27 41 0.29<br />
162 Medium 2129 2642 0.105 6.65 1060 0.024 0.46 0.4 55 0.34<br />
167 Medium + 2186 2707 0.107 6.95 1080 0.024 0.47 0.44 59 0.35<br />
175 High 2277 2812 0.112 7.45 1112 0.025 0.5 0.5 66 0.38<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH9CH<br />
152 Extra low 2093 2662 0.106 4.19 1200 0.027 0.7 0.23 30 0.20<br />
190 Low 2586 3269 0.13 6.1 1422 0.032 0.96 0.3 42 0.22<br />
221 Low + 2951 3693 0.147 7.62 1556 0.035 1.14 0.39 55 0.25<br />
274 Medium 3584 4438 0.176 10.67 1798 0.04 1.49 0.57 80 0.29<br />
282 Medium + 3675 4541 0.18 11.13 1829 0.041 1.54 0.62 86 0.30<br />
304 High 3923 4828 0.192 12.45 1914 0.043 1.67 0.74 104 0.34<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH12CH<br />
216 Extra low 3091 4016 0.159 9.92 1699 0.038 1.5 0.32 42 0.19<br />
235 Low 3326 4295 0.17 11.21 1784 0.04 1.65 0.4 54 0.23<br />
262 Low + 3659 4687 0.186 13.16 1904 0.042 1.86 0.5 67 0.26<br />
307 Medium 4210 5343 0.212 16.72 2102 0.047 2.23 0.7 93 0.30<br />
326 Medium + 4463 5658 0.225 18.57 2206 0.049 2.44 0.82 113 0.35<br />
335 High 4569 5783 0.229 19.33 2243 0.05 2.52 0.89 121 0.36<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH13CH<br />
236 Extra low 3353 4338 0.172 7.86 1934 0.043 2.15 0.34 45 0.19<br />
265 Low 3738 4817 0.191 9.52 2103 0.047 2.51 0.4 54 0.20<br />
317 Low + 4376 5572 0.221 12.45 2340 0.052 3.06 0.51 70 0.22<br />
363 Medium 4937 6239 0.248 15.32 2547 0.057 3.58 0.7 99 0.27<br />
381 Medium + 5184 6552 0.26 16.77 2658 0.059 3.87 0.78 110 0.29<br />
431 High 5774 7241 0.287 20.16 2863 0.064 4.45 1.06 143 0.33<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH15CH<br />
246 Extra low 3475 4480 0.178 6.57 2057 0.046 2.78 0.32 42 0.17<br />
280 Low 3980 5151 0.204 8.5 2336 0.052 3.52 0.37 49 0.18<br />
324 Low + 4589 5927 0.235 11.01 2625 0.058 4.36 0.47 65 0.20<br />
380 Medium 5282 6749 0.268 14 2886 0.064 5.2 0.64 90 0.24<br />
415 Medium + 5714 7265 0.288 16.04 3047 0.068 5.75 0.77 111 0.27<br />
440 High 6021 7633 0.303 17.57 3163 0.07 6.15 0.88 124 0.28<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH18CH<br />
350 Extra low 4901 6288 0.25 8.75 2971 0.066 6.61 0.47 60 0.17<br />
382 Low 5378 6921 0.275 10.46 3239 0.072 7.74 0.51 67 0.18<br />
449 Low + 6237 7966 0.316 13.59 3599 0.08 9.4 0.65 90 0.20<br />
538 Medium 7333 9277 0.368 18.06 4020 0.089 11.52 0.9 129 0.24<br />
585 Medium + 7910 9966 0.395 20.65 4241 0.094 12.71 1.01 142 0.24<br />
647 High 8703 10936 0.434 24.55 4566 0.102 14.55 1.24 177 0.27<br />
Based on following Design Condition:<br />
Return Air Temperature(summer): 23 o C db and 16.4 o C wb<br />
Chilled Water Temperature: 6/12 o C<br />
Return Air Temperature(winter): 21 o C<br />
LPHW Temperature: 82/71 o C<br />
External Static Pressure: 30Pa<br />
Electric heat is available on all units. For further information please contact us.<br />
For any alternative design conditions please contact the Cooling Department at <strong>Diffusion</strong>.
ACOUSTIC PERFORMANCE<br />
SOUND POWER LEVELS<br />
Model & Size<br />
Air Volume l/s<br />
Speed<br />
Acoustic Measuring Position<br />
OCTAVE BAND FREQUENCY<br />
63 125 250 500 1K 2K 4K<br />
NR<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH6CH<br />
109 Extra low<br />
122 Low<br />
143 Low +<br />
162 Medium<br />
167 Medium +<br />
175 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
42 48 43 45 34 28 25<br />
47 46 38 31 32 22 21<br />
41 49 45 47 37 31 29<br />
48 48 39 32 34 24 23<br />
43 51 47 49 40 34 32<br />
48 50 43 34 37 27 26<br />
46 52 49 51 41 37 35<br />
51 52 45 36 39 29 29<br />
45 53 49 51 42 37 36<br />
50 52 46 37 41 30 30<br />
47 54 52 54 44 39 36<br />
52 56 49 38 42 31 30<br />
28<br />
31<br />
33<br />
35<br />
36<br />
37<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH9CH<br />
152 Extra low<br />
190 Low<br />
221 Low +<br />
274 Medium<br />
282 Medium +<br />
304 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
47 48 43 44 34 27 21<br />
46 46 41 30 29 19 17<br />
46 49 45 47 37 30 25<br />
47 48 43 32 32 21 20<br />
49 51 47 49 39 33 28<br />
48 50 45 34 35 23 23<br />
46 53 50 52 43 38 34<br />
49 53 48 38 39 28 28<br />
46 54 51 53 44 39 35<br />
51 53 49 38 40 29 29<br />
47 55 53 54 45 40 37<br />
51 54 50 39 41 30 31<br />
28<br />
30<br />
32<br />
35<br />
36<br />
37<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH12CH<br />
216 Extra low<br />
235 Low<br />
262 Low +<br />
307 Medium<br />
326 Medium +<br />
335 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
45 48 43 45 33 27 22<br />
47 47 40 31 30 18 17<br />
48 49 46 48 36 30 26<br />
45 48 42 32 33 22 20<br />
45 51 48 50 39 33 29<br />
49 50 44 35 35 24 22<br />
47 52 51 51 41 36 34<br />
49 53 48 38 39 28 27<br />
48 54 53 53 44 38 36<br />
51 54 49 39 41 29 29<br />
48 54 53 54 44 39 37<br />
51 54 50 39 41 30 30<br />
28<br />
30<br />
33<br />
35<br />
36<br />
37<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH13CH<br />
236 Extra low<br />
265 Low<br />
317 Low +<br />
363 Medium<br />
381 Medium +<br />
431 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
48 49 45 45 34 27 22<br />
45 47 41 30 28 18 18<br />
47 50 46 47 36 29 24<br />
47 49 43 32 30 20 19<br />
48 52 48 49 38 32 28<br />
48 50 44 34 33 23 22<br />
48 54 51 52 42 35 32<br />
49 53 47 37 37 27 26<br />
51 55 53 53 43 37 34<br />
50 54 48 38 38 28 27<br />
52 56 54 54 45 39 37<br />
52 56 50 41 41 32 31<br />
28<br />
30<br />
32<br />
35<br />
36<br />
37<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH15CH<br />
246 Extra low<br />
280 Low<br />
324 Low +<br />
380 Medium<br />
415 Medium +<br />
440 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
45 50 45 45 33 26 21<br />
46 47 42 31 29 19 17<br />
44 51 46 46 34 28 22<br />
46 48 43 34 31 20 18<br />
44 52 48 49 37 30 26<br />
46 49 46 35 34 22 21<br />
46 53 49 50 40 31 27<br />
51 53 49 37 37 26 25<br />
52 55 53 53 43 37 34<br />
52 54 50 39 40 28 27<br />
52 56 53 54 44 38 36<br />
51 55 51 40 41 30 28<br />
28<br />
30<br />
32<br />
35<br />
37<br />
38<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong><br />
WH18CH<br />
350 Extra low<br />
382 Low<br />
449 Low +<br />
538 Medium<br />
585 Medium +<br />
647 High<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
INLET CASE RADIATED<br />
DISCHARGE<br />
52 48 46 44 35 26 20<br />
46 47 41 33 28 22 18<br />
52 49 47 45 35 28 22<br />
48 49 43 35 29 23 20<br />
50 50 49 47 37 31 25<br />
50 50 45 35 29 21 20<br />
52 53 52 51 41 35 31<br />
50 52 48 37 33 24 25<br />
51 55 53 52 42 36 33<br />
52 53 48 39 35 26 26<br />
51 55 54 53 44 38 35<br />
53 55 50 41 38 29 29<br />
28<br />
30<br />
32<br />
35<br />
36<br />
37<br />
OCTAVE BAND FREQUENCY<br />
63 125 250 500 1K 2K 4K<br />
CORR<strong>EC</strong>TIONS FOR DISCHARGE INDUCT<br />
8 4 1 0 0 0 0<br />
Correction to be added to Discharge only, to convert to Discharge Induct.<br />
The discharge sound power levels shown above are based on all front spigots connected directly to an unlined<br />
plenum/grilles and measurements taken 1.5m from grille at 45 o .<br />
The NR levels shown above are for guidance only and are based on a typical office layout. We would recommend<br />
that advice is taken from an Acoustic Consultant to verify actual project noise levels.<br />
To achieve guide NR35 it is recommended that a maximum velocity of 2.5m/s per outlet is not exceeded.
<strong>Highline</strong> <strong>260i</strong> <strong>EC</strong> <strong>Waterside</strong> <strong>Fan</strong> <strong>Coil</strong> <strong>Unit</strong><br />
UNIT A SPIGOTS<br />
(No Off)<br />
6 855 4<br />
9 1075 5<br />
12 1230 5<br />
13 1408 5<br />
15 1655 6<br />
18 2040 7<br />
R<strong>EC</strong>TANGULAR SPIGOTS<br />
ALSO AVAILABLE
Options<br />
• Underfloor installation available<br />
• Electric Heat(Stainless Steel sheathed element) with Thermal Cut-out<br />
• Differential Pressure Switch for heating element protection(Standard)<br />
• Current Switch for heating element protection(Optional)<br />
• Power Correction Module<br />
• Speed Controller/ Speed Limiter<br />
• 24v Transformer<br />
• Condensate pumps<br />
DIFFUSION <strong>Unit</strong> Coding System<br />
UNIT MODEL FAN TYPE CONTROL APPLICATION OPTIONS UNIT SIZE Chassis<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong> - Electronically commutated A - Airside H - Horizontal E - EL<strong>EC</strong>TRIC 06 CH<br />
W - <strong>Waterside</strong> UF - Underfloor CO - COOLING ONLY 09<br />
e.g.<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong>-W-H-09-CH<br />
HIGHLINE <strong>260i</strong>, with <strong>EC</strong> fans, <strong>Waterside</strong> Horizontal, 4 pipe, size 9, chassis<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong>-W-UF-CO-09-CH<br />
HIGHLINE <strong>260i</strong>, with <strong>EC</strong> fans, <strong>Waterside</strong> Underfloor, Cooling Only, size 9, chassis<br />
HIGHLINE <strong>260i</strong> <strong>EC</strong>-W-H-E-09-CH<br />
HIGHLINE <strong>260i</strong>, with <strong>EC</strong> fans, <strong>Waterside</strong> Horizontal, 2 pipe, Electric Heat, size 9, chassis<br />
12<br />
13<br />
15<br />
18<br />
‘<br />
Established in 1960,<br />
<strong>Diffusion</strong> has over 40 years<br />
experience in producing<br />
environmental solutions<br />
via the manufacture of heating,<br />
air conditioning and<br />
ventilating products.<br />
‘<br />
<strong>Diffusion</strong> Environmental Systems<br />
47 Central Avenue, West Molesey, Surrey KT8 2QZ<br />
Tel: (+44) 020 8783 0033 Fax: (+44) 020 8783 0140<br />
Email: diffusion@etenv.co.uk www.diffusion-group.co.uk<br />
<strong>Diffusion</strong> Environmental Systems have a policy of continuous<br />
development. We therefore reserve the right to alter information<br />
contained in this leaflet, without prior notice.