Microprocessor controller<br />
All units are equipped with an electronic programmable control<br />
system. This allows complete management of all the functions of<br />
the unit and ensures protection of all vital parts. It has a<br />
diagnostics function, permitting easy and straightforward<br />
understanding of all the possible failures and malfunctions of the<br />
unit. All functions and indicators appear on the LCD screen. Over<br />
<strong>150</strong> programmable parameters offer complete unit management.<br />
Critical parameters that require control are:<br />
ñ Start-up shut down time of compressor.<br />
ñ Time delay.<br />
ñ Protection against multiple start-up.<br />
ñ Water pump time delay in reference to compressor operation.<br />
ñ Inlet/outlet water temperature.<br />
ñ Air heat exchanger temperature.<br />
Controlled operational parameters<br />
ñ Water temperature adjustment in the inlet side during summer<br />
operation*.<br />
ñ Water outlet temperature adjustment in summer operation**.<br />
ñ Water temperature adjustment in the inlet side during winter<br />
operation*.<br />
ñ Water outlet temperature adjustment in winter operation*.<br />
ñ Compressor capacity control.<br />
Controlled fault parameters<br />
ñ Low suction pressure per refrigerant circuit.<br />
ñ High discharge pressure per refrigerant circuit.<br />
ñ Compressor overload.<br />
ñ Fan motor overload.<br />
ñ Water pump overload.<br />
ñ Flow switch fault.<br />
ñ Water sensor error due to bad contact or sensor failure.<br />
ñ Error reading in water outlet low temperature.<br />
ñ Compressor operating hour reading.<br />
In addition the control also includes<br />
ñ Self diagnostic error of all electronic control sensors.<br />
ñ Remote on/ off switch.<br />
ñ Remote alarm indication capability.<br />
ñ Remote cool/heat selector switch.<br />
ñ History of operation points and fault codes**.<br />
ñ Password access code.<br />
Refrigerant circuit<br />
The units have multiple refrigerant circuits depending on the size<br />
one per tandem compressor.<br />
Each circuit consists of the following:<br />
ñ Thermal expansion valve.<br />
ñ Filter drier with a replaceable core.<br />
ñ Shut off valves.<br />
ñ Two way solenoid valve.<br />
ñ Sight glass for checking the liquid lines.<br />
ñ 4-way reversing valve.<br />
ñ Suction accumulator.<br />
ñ Liquid receiver.<br />
ñ Check valve.<br />
ñ High and low pressure gauges for each refrigerant circuit,<br />
easily viewed.<br />
ñ Service valves.<br />
ñ Unit protection is provided by a high pressure switch with<br />
manual reset, low pressure protection is a low-pressure<br />
switch with auto reset.<br />
ñ Flexible refrigerant pipe on the compressor discharge and<br />
suction lines to avoid vibration and noise.<br />
Optional accessories<br />
Microprocessor controller options<br />
ñ BMS module interface kit for Bacnet, Lon Works and Trend<br />
connection**.<br />
ñ BMS interface kit for Modbus connection.<br />
ñ Connection via internet using a device converting the Carel<br />
protocol to 10Mb/s TCP/IP ethernet protocol**.<br />
ñ Possibility to send and receive messages using a GSM<br />
modem**.<br />
ñ Communication card through RS232 / RS485 serial ports.<br />
ñ Extended memory card for up to five thousands messages**.<br />
ñ Extended memory card 1&2 MB**.<br />
ñ Parallel chiller operation with standard controller for units<br />
with a maximum of eight compressors**.<br />
ñ Microprocessor parameter reprogramming card.<br />
ñ Compressor running current**.<br />
ñ Self diagnostic and adaptive control**.<br />
Other unit accessories/option<br />
ñ R407c or R22 refrigerant.<br />
ñ Condenser fins made of copper or prepainted aluminum, and<br />
Blygold treatment for corrosion protection.<br />
ñ Glycol for chilled water temperature down to –5 o C.<br />
ñ Continuous linear fan speed regulation.<br />
ñ High pressure relief valve on compressor discharge.<br />
ñ A-meter, V-meter.<br />
ñ Compressor noise reduction jacket.<br />
ñ Electrical board ventilation fan.<br />
ñ Water heat exchanger antifreezing electrical heater.<br />
ñ Other custom built options upon request.<br />
* For models <strong>055</strong>-<strong>085</strong><br />
** For models <strong>090</strong> – 170<br />