Microprocessor controller<br />

All units are equipped with an electronic programmable control<br />

system. This allows complete management of all the functions of<br />

the unit and ensures protection of all vital parts. It has a<br />

diagnostics function, permitting easy and straightforward<br />

understanding of all the possible failures and malfunctions of the<br />

unit. All functions and indicators appear on the LCD screen. Over<br />

<strong>150</strong> programmable parameters offer complete unit management.<br />

Critical parameters that require control are:<br />

ñ Start-up shut down time of compressor.<br />

ñ Time delay.<br />

ñ Protection against multiple start-up.<br />

ñ Water pump time delay in reference to compressor operation.<br />

ñ Inlet/outlet water temperature.<br />

ñ Air heat exchanger temperature.<br />

Controlled operational parameters<br />

ñ Water temperature adjustment in the inlet side during summer<br />

operation*.<br />

ñ Water outlet temperature adjustment in summer operation**.<br />

ñ Water temperature adjustment in the inlet side during winter<br />

operation*.<br />

ñ Water outlet temperature adjustment in winter operation*.<br />

ñ Compressor capacity control.<br />

Controlled fault parameters<br />

ñ Low suction pressure per refrigerant circuit.<br />

ñ High discharge pressure per refrigerant circuit.<br />

ñ Compressor overload.<br />

ñ Fan motor overload.<br />

ñ Water pump overload.<br />

ñ Flow switch fault.<br />

ñ Water sensor error due to bad contact or sensor failure.<br />

ñ Error reading in water outlet low temperature.<br />

ñ Compressor operating hour reading.<br />

In addition the control also includes<br />

ñ Self diagnostic error of all electronic control sensors.<br />

ñ Remote on/ off switch.<br />

ñ Remote alarm indication capability.<br />

ñ Remote cool/heat selector switch.<br />

ñ History of operation points and fault codes**.<br />

ñ Password access code.<br />

Refrigerant circuit<br />

The units have multiple refrigerant circuits depending on the size<br />

one per tandem compressor.<br />

Each circuit consists of the following:<br />

ñ Thermal expansion valve.<br />

ñ Filter drier with a replaceable core.<br />

ñ Shut off valves.<br />

ñ Two way solenoid valve.<br />

ñ Sight glass for checking the liquid lines.<br />

ñ 4-way reversing valve.<br />

ñ Suction accumulator.<br />

ñ Liquid receiver.<br />

ñ Check valve.<br />

ñ High and low pressure gauges for each refrigerant circuit,<br />

easily viewed.<br />

ñ Service valves.<br />

ñ Unit protection is provided by a high pressure switch with<br />

manual reset, low pressure protection is a low-pressure<br />

switch with auto reset.<br />

ñ Flexible refrigerant pipe on the compressor discharge and<br />

suction lines to avoid vibration and noise.<br />

Optional accessories<br />

Microprocessor controller options<br />

ñ BMS module interface kit for Bacnet, Lon Works and Trend<br />

connection**.<br />

ñ BMS interface kit for Modbus connection.<br />

ñ Connection via internet using a device converting the Carel<br />

protocol to 10Mb/s TCP/IP ethernet protocol**.<br />

ñ Possibility to send and receive messages using a GSM<br />

modem**.<br />

ñ Communication card through RS232 / RS485 serial ports.<br />

ñ Extended memory card for up to five thousands messages**.<br />

ñ Extended memory card 1&2 MB**.<br />

ñ Parallel chiller operation with standard controller for units<br />

with a maximum of eight compressors**.<br />

ñ Microprocessor parameter reprogramming card.<br />

ñ Compressor running current**.<br />

ñ Self diagnostic and adaptive control**.<br />

Other unit accessories/option<br />

ñ R407c or R22 refrigerant.<br />

ñ Condenser fins made of copper or prepainted aluminum, and<br />

Blygold treatment for corrosion protection.<br />

ñ Glycol for chilled water temperature down to –5 o C.<br />

ñ Continuous linear fan speed regulation.<br />

ñ High pressure relief valve on compressor discharge.<br />

ñ A-meter, V-meter.<br />

ñ Compressor noise reduction jacket.<br />

ñ Electrical board ventilation fan.<br />

ñ Water heat exchanger antifreezing electrical heater.<br />

ñ Other custom built options upon request.<br />

* For models <strong>055</strong>-<strong>085</strong><br />

** For models <strong>090</strong> – 170<br />

Interklima Hydronic systems<br />

<strong>LPCA</strong> <strong>055</strong>-<strong>170HMB</strong> ñ R407c/Tandem Scroll 5