10.4 Watercharge, flow and quality<br />

To ensure proper operation of the unit, a minimum water volume<br />

is required in the system and the water flow must be within the<br />

operation range as specified in the table.<br />

<strong>LPCA</strong> <strong>055</strong>HMB<br />

<strong>LPCA</strong> <strong>060</strong>HMB<br />

<strong>LPCA</strong> <strong>070</strong>HMB<br />

<strong>LPCA</strong> <strong>075</strong>HMB<br />

<strong>LPCA</strong> <strong>085</strong>HMB<br />

<strong>LPCA</strong> <strong>090</strong>HMB<br />

<strong>LPCA</strong> <strong>100</strong>HMB<br />

<strong>LPCA</strong> <strong>115</strong>HMB<br />

<strong>LPCA</strong> <strong>125</strong>HMB<br />

<strong>LPCA</strong> <strong>135</strong>HMB<br />

<strong>LPCA</strong> <strong>150</strong>HMB<br />

<strong>LPCA</strong> <strong>170HMB</strong><br />

Minim um<br />

water<br />

volume (l)<br />

1129<br />

1288<br />

1445<br />

1604<br />

1794<br />

1931<br />

2168<br />

2405<br />

2690<br />

2891<br />

3207<br />

3587<br />

Minim um<br />

water flow<br />

(l/h)<br />

14788<br />

16855<br />

18914<br />

20964<br />

23456<br />

25286<br />

28366<br />

31455<br />

35188<br />

37819<br />

41937<br />

46912<br />

Nominal<br />

water flow<br />

(l/h)<br />

32370<br />

36911<br />

41435<br />

45976<br />

51428<br />

55367<br />

62161<br />

68955<br />

77<strong>125</strong><br />

82887<br />

91934<br />

102839<br />

Maxim um<br />

water flow<br />

(l/h)<br />

38915<br />

44000<br />

49773<br />

50000<br />

5<strong>100</strong>0<br />

66543<br />

69000<br />

7<strong>100</strong>0<br />

92601<br />

99524<br />

103000<br />

104000<br />

Be sure the water quality is in accordance with the specifications<br />

below<br />

NOTES<br />

The above tables are purely<br />

indicative and non-binding<br />

Items<br />

Items to be controlled:<br />

PH AT 25 Ô C<br />

∂lectrical conduct (mS/m) at 25 Ô C<br />

Chloride ion (mg CI-/I)<br />

Sulfate ion (mg SO 2/4/I<br />

M-alkalinity (ph 4.8) (mg SO3/I)<br />

Total hardness (mg CaCO3/I )<br />

Calcium hardness (mg CaCO3/I)<br />

Silica ion (mg SiO2/I<br />

Items to be referred to:<br />

Iron (mg Fe/I)<br />

Copper (mg Cu/I)<br />

Sulfide ion (mg S2-/I)<br />

Amonium ion (mg NH+4/I<br />

Remaining chloride (mg CI/I)<br />

Free carbide (mg SO2/I)<br />

Stability index<br />

Circulating<br />

water 20C<br />

Evaporator water<br />

6.8 - 8.0<br />

below 30<br />

below 50<br />

below 50<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 1.0<br />

below 1.0<br />

Not detectable<br />

below 0.3<br />

below 0.25<br />

below 0.4<br />

-<br />

Supply water<br />

6.8 - 8.0<br />

below 30<br />

below 200<br />

below 50<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 0.3<br />

below 0.1<br />

Not detectable<br />

below 0.1<br />

below 0.3<br />

below 4.0<br />

-<br />

Circulating<br />

water 20C-60C<br />

7.0 - 8.0<br />

below 30<br />

below 30<br />

below 30<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

Heated water<br />

below 1.0<br />

below 1.0<br />

Not detectable<br />

below 0.1<br />

below 0.1<br />

below 0.4<br />

-<br />

Supply water<br />

7.0 - 8.0<br />

below 30<br />

below 30<br />

below 30<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 0.3<br />

below 1.0<br />

Not detectable<br />

below 0.1<br />

below 0.3<br />

below 4.0<br />

-<br />

Tendency<br />

if out of criteria<br />

corrosion + scale<br />

corrosion + scale<br />

corrosion<br />

corrosion<br />

scale<br />

scale<br />

scale<br />

scale<br />

corrosion + scale<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion + scale<br />

10.5 Operating pressure of the<br />

refrigerant circuit<br />

It is important to check the high and low pressure of the<br />

refrigerant circuit to ensure the proper operation of the<br />

unit and to guarantee that the rated output shall be<br />

obtained.<br />

Cooling mode<br />

(region)<br />

low pressure<br />

high pressure<br />

Minim um<br />

(outdoor temp. 15 Ô Nominal<br />

CDB)<br />

(leaving water temp 6 Ô (outdoor temp. 35 Ô Maximum<br />

CDB)<br />

C) (leaving water temp, 7 Ô (outdoor temp. 38 Ô CDB)<br />

C) (leaving water temp, 25 Ô C)<br />

3,5-4 bar<br />

17-19 bar<br />

4-5 bar<br />

21-23 bar<br />

5,5-6 bar<br />

24-26 bar<br />

Attention:<br />

The pressures measured shall vary between a maximum<br />

and minimum value, depending on the water and out<br />

door temperatures at the moment of measurement.<br />

Heating mode<br />

(region)<br />

low pressure<br />

high pressure<br />

Minim um<br />

(outdoor temp. -5 Ô CDB)<br />

Nominal<br />

(outdoor temp. 7 Ô CDB)<br />

Maximum<br />

(outdoor temp. 21 Ô CDB)<br />

(leaving water temp 25 Ô C) (leaving water temp, 45 Ô C) (leaving water temp, 50 Ô C)<br />

2.5-3 bar<br />

15-18 bar<br />

3-3.5 bar<br />

21-23 bar<br />

3,5-5 bar<br />

25-26 bar<br />

26<br />

Interklima Hydronic systems<br />

<strong>LPCA</strong> <strong>055</strong>-<strong>170HMB</strong> ñ R407c/Tandem Scroll