10.3 Recommendations concerning the hydraulic circuit<br />
ñ All field connections must be provided by a licensed technician<br />
and must comply with the applicable local and national codes.<br />
ñ Evaporator water connections should be made in accordance<br />
with the unit outlook respecting the water inlet – and outlets.<br />
ñ Water piping to be arranged so that the circulating pump<br />
discharges directly into the evaporator.<br />
ñ Install a flow switch or water differential pressostat (standard<br />
component) in the water outlet piping to prevent the unit from<br />
operating at a water flow, which is too low. A terminal is provided<br />
in the switch box for the electrical connection of the flow switch<br />
in the control circuit.<br />
ñ To avoid erosion, it is recommended to install a filter in the<br />
water inlet pipe.<br />
ñ It is essential to install a thermometer in the water inlet/ outlet<br />
pipe to check temperatures.<br />
ñ Provide heat insulation with suitable vapour barrier around the<br />
chilled water piping to prevent condensation and capacity loss.<br />
ñ Provide drain connections at all low points of the system to<br />
permit complete drainage for maintenance and/ or shutdown.<br />
ñ Air vents should be provided at all high points in the system<br />
located were they are easily accessible for servicing. The<br />
water inlet pipe is specially designed to obtain a complete air<br />
purge of the evaporator.<br />
ñ Install an expansion tank on the suction side of the water pump<br />
so that the water pressure on the pump suction will be positive.<br />
ñ To avoid frequent on/off operation of the compressor, a<br />
minimum water volume is required in the system (table 10.4).<br />
ñ To assure proper operation of the unit, the water flow through<br />
the evaporator must be within the specified limits in (table<br />
10.4).<br />
7<br />
15<br />
13<br />
3<br />
1 2<br />
4<br />
5<br />
6<br />
5<br />
14<br />
5<br />
7<br />
3<br />
1<br />
16<br />
2 9<br />
10<br />
4<br />
5<br />
5<br />
11<br />
8<br />
12<br />
5<br />
8<br />
Example with one central pump<br />
24<br />
Interklima Hydronic systems<br />
<strong>LPCA</strong> <strong>055</strong>-<strong>170HMB</strong> ñ R407c/Tandem Scroll