U-MHST Series - Siemens Building Technologies
U-MHST Series - Siemens Building Technologies
U-MHST Series - Siemens Building Technologies
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
U-<strong>MHST</strong> <strong>Series</strong><br />
Synchronous Temporal Electronic Horn / Strobes<br />
ENGINEER AND ARCHITECT SPECIFICATIONS<br />
• Universal Mount: 1, 2 Gang or 4” Square Back<br />
Box Mounting<br />
• Synchronous Horn or Horn / Strobe Units<br />
• 24 Vdc Units Available with 15/75, 30/75,<br />
60/75, 75 or 110 Candela Strobes<br />
• Must Be Used With SCM-F or DSC Synchronized<br />
Control Units<br />
• Only One Pair of Wires Out of DSC Dual Sync<br />
Control Unit Required<br />
• Light Plastic Grill Construction<br />
• ADA/UL 1971 Horn-Strobe Versions<br />
• Screw Terminals Accept #12 AWG<br />
• Available for Wall or Ceiling Mount Applications<br />
• Ceiling Mount Devices Available in Red or<br />
White<br />
• Wall Mount Devices Available in Red or White<br />
• Listed, CSFM, NYMEA, FM & ULC<br />
Approvals Pending<br />
Cerberus Division<br />
Description<br />
Cerberus Pyrotronics’ series of Synchronous Electronic<br />
Horn / Horn Strobes provide synchronous strobes with<br />
temporal tone signals on one pair of wires. Two notification<br />
output circuits are required: one non-silenceable - for<br />
strobes and one for silenceable signals.<br />
The new U-<strong>MHST</strong> series horn operates on a current of<br />
23ma at 24Vdc, The audio portion of the signal provides a<br />
temporal 95dB tone output. The U-<strong>MHST</strong>-1G mounts to a<br />
single gang, the U-<strong>MHST</strong> horn or U-<strong>MHST</strong> horn/strobe are<br />
either 1, 2 gang or 4” square mounting.<br />
Cerberus Pyrotronics’ notification devices are designed with<br />
the installer in mind. The U-<strong>MHST</strong> series devices are<br />
constructed with all of the electronics in the housing and<br />
not in the box. This design helps eliminate possible ground<br />
faults from jamming wires and devices in the box. Units<br />
are also available in two different colors, red or white.<br />
The U-<strong>MHST</strong>/Strobe construction consists of a Xenon<br />
flashtube with solid state circuitry for maximum reliability<br />
and efficiency. Full range of candella series strobes have a<br />
rounded dome shape made of clear Lexan ® . “FIRE” letters<br />
are visible on the front mounting plate. The overall lens is<br />
2.0” x 2 7/8” with a height of 1 3/8”.<br />
U-<strong>MHST</strong> series synchronous strobes must be used with<br />
either SCM-F or DSC (Dual Sync Control) modules.<br />
To order a device in “white” use a “-W” at the end of the<br />
model number (i.e., U-<strong>MHST</strong>-W).<br />
CATALOG NUMBER<br />
2540
Ordering Information<br />
U-<strong>MHST</strong> <strong>Series</strong> Horn Wall Mount<br />
Model Number<br />
Description<br />
Part<br />
Number<br />
Horn<br />
Current<br />
U-<strong>MHST</strong> <strong>Series</strong> Horn/Strobe Wall Mount<br />
dB Rating<br />
@ 10'<br />
U-<strong>MHST</strong>-1G Electronic Horn 24VDC 500-696628 23 ma 95 db<br />
U-<strong>MHST</strong>-1G-W Electronic Horn 24VDC 500-696629 23 ma 95 db<br />
U-<strong>MHST</strong> Electronic Horn 24VDC 500-696630 23 ma 95 db<br />
U-<strong>MHST</strong>-W Electronic Horn 24VDC 500-696631 23 ma 95 db<br />
Model Number<br />
Description<br />
Part<br />
Number<br />
Strobe<br />
Current<br />
Horn<br />
Current<br />
dB Rating<br />
@ 10'<br />
U-<strong>MHST</strong>-S17S 15/75CD Sync 500-696632 59 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S17S-W 15/75CD Sync 500-696633 59 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S30S 30/75CD Sync 500-696634 88 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S30S-W 30/75CD Sync 500-696635 88 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S60S 60/75CD Sync 500-696636 155 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S60S-W 60/75CD Sync 500-696637 155 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S75S 75CD Sync 500-696638 170 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S75S-W 75CD Sync 500-696639 170 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S110S 110CD Sync 500-696640 249 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S110S-W 110CD Sync 500-696641 249 ma 23 ma 95 db<br />
Control Module Specifications:<br />
SCM-F Module Operating Voltage : 20 TO 31 Vdc or VFW<br />
SCM-F Module Operating Current: Non-Silenceable NAC side 55ma,<br />
Silenceable NAC side 5m<br />
Maximum Current Output: 3 Amps Max. not to exceed NAC rating<br />
DSC Module Operating Votage: 20 to 31 Vdc or VFW<br />
DSC Module Operating Current: Non-Silenceable NAC side 55mA,<br />
Silenceable NAC side .005 Amps.<br />
Maximum Current Output: 3 Amps max. not to exceed NAC rating<br />
1, 2 or 4 Square Mounting<br />
U-<strong>MHST</strong> <strong>Series</strong> Horn/Strobe Ceiling Mount<br />
Model Number<br />
Description<br />
Part<br />
Number<br />
Strobe<br />
Current<br />
Horn<br />
Current<br />
dB<br />
Rating @<br />
10'<br />
U-<strong>MHST</strong>-S17S-C 15/75CD Sync 500-696894 59 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S17S-W-C 15/75CD Sync 500-696895 59 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S30S-C 30/75CD Sync 500-696896 88 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S30S-W-C 30/75CD Sync 500-696897 88 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S60S-C 60/75CD Sync 500-696898 155 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S60S-W-C 60/75CD Sync 500-696899 155 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S75S-C 75CD Sync 500-696900 170 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S75S-W-C 75CD Sync 500-696901 170 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S110S-C 110CD Sync 500-696902 249 ma 23 ma 95 db<br />
U-<strong>MHST</strong>-S110S-W-C 110CD Sync 500-696903 249 ma 23 ma 95 db<br />
For wiring diagram for U-<strong>MHST</strong> <strong>Series</strong> Horn/Strobes refer to Installation<br />
Instruction Sheet<br />
Listed operating range is 20 to 31 VDC/FWR<br />
Minimum UL measurements are 82dB at 24VDC/FWR taken in free air<br />
at 360° around the device and averaged. Typical readings are frontal<br />
sound readings taken with a dB meter with signal mounted on wall.<br />
Rated for indoor use 32°F to 120°F, (0°C to 49°C), at RH 85%.<br />
(-C : Ceiling Mounted)<br />
(-W: White)<br />
<strong>Siemens</strong> <strong>Building</strong> <strong>Technologies</strong><br />
Cerberus Division<br />
Cerberus Division<br />
8 Fernwood Road<br />
Florham Park, NJ 07932<br />
Tel: (973) 593-2600<br />
FAX: (973) 593-6670<br />
Website: www.cerbpyro.com<br />
3/00<br />
10M<br />
SCD-IG<br />
Printed in U.S.A.<br />
Cerberus Division<br />
50 East Pearce Street<br />
Richmond Hill, Ontario<br />
L4B, 1B7 CN<br />
Tel: (905) 764-8384<br />
FAX: (905) 731-9182<br />
March 2000<br />
Supersedes sheet dated 2/99