19.01.2015 Views

MOTEMP S 90 WL

MOTEMP S 90 WL

MOTEMP S 90 WL

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TempLine<br />

<strong>MOTEMP</strong><br />

S <strong>90</strong> <strong>WL</strong><br />

Temperature<br />

Control Units<br />

Operating Manual<br />

CE<br />

05 / 2005 312A-00.0.EN V0.0<br />

07 / 02 - 1 -


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

Copyright<br />

© 2005 Motan GmbH, D-88316 Isny im Allgäu<br />

This operating manual is copyright; all rights reserved. This operating manual may only be<br />

reproduced, even in part, with the approval of Motan GmbH only. Anyone violating this provision may<br />

be required to pay damages and may be subject to criminal penalties.<br />

The technical information and operation instructions in the operating and maintenance manual apply<br />

to the most recent delivery version of the dry air generator.<br />

Manufacturer's address<br />

Motan GmbH Telephone: +49 (0) 7562 / 76-0<br />

Max-Eyth-Weg 42 Fax: +49 (0) 7562 / 76-111<br />

D-88316 Isny im Allgäu motan.ger.s@motan.de<br />

Germany<br />

http://www.motan.com<br />

2<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

2.6 Switching on<br />

2.6.1 Operating and display elements<br />

“Page up” for queries and programming (separate RT60 Operating Instructions).<br />

“Page down” for queries and programming ( separate RT60 Operating Instructions).<br />

Up, increase value. Set-point input, queries and programming.<br />

Down, decrease value. Set-point input, queries and programming.<br />

ON/OFF key with LED.<br />

Leak-stop mode key with LED.<br />

Suction mode key with LED.<br />

Alarm reset key with LED.<br />

1 Display field for actual value at temperature<br />

sensor and outlet setting value S1<br />

2 Display field for set-point value (SP)<br />

and setting values<br />

3 LED for display in °C<br />

4 LED for display in °F<br />

5 Heating LED<br />

6 Cooling LED<br />

1<br />

5<br />

6<br />

3<br />

4<br />

2<br />

Fig. 1: Operating and display elements<br />

8<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

2.6.2 Switching on<br />

After checking the consumer, connecting the hoses and establishing the electrical connections,<br />

proceed as follows:<br />

Initial set-up / filling the thermal oil<br />

1 Open the vent valve at the consumer as well as the shut-off valve (when present).<br />

2 Actuate the unit’s main switch. Once the unit has been switched on, the RT60 control system will<br />

run a functional test for approximately 3 seconds. During this test, four dots will appear in each of<br />

the two display fields. Once the test has been successfully completed, the dots will disappear,<br />

indicating that the RT60 is ready for operation.<br />

“FILL” will appear in the upper display field and “Err” in the lower. The acoustic group interrupt is<br />

activated; it can be reset by pressing the ALARM RESET key. The displays will alternate<br />

between “OFF” and “FILL” “Err”.<br />

3 Press the ON/OFF key. The displays will now alternate between<br />

“set-point”, “Actual value”,and “FILL” “Err”. Should a different<br />

message appear, see Section 3.1 and separate RT60 Operating<br />

lnstructions.<br />

4 Water will fill automatically. The unit can also be filled via the<br />

manual fillingport situated on the tank lid (1, Fig. 2,)<br />

1<br />

5 Press the ALARM RESET key. Enter the desired set-point value<br />

using the keys<br />

6 To set other values, please refer to the RT60 Operating Instructions<br />

Fig. 2: Filling port<br />

7 Check the temperature control circuit (unit, hoses, consumer, etc.)<br />

for leakage<br />

8 Close the consumer vent valve once water flows out of it regularly.<br />

Switching on after initial set-up<br />

1 Open consumer vent valve as well as shut-off valve (when present).<br />

2 Actuate the unit’s main switch. Once the unit has been switched on, the RT60 control system<br />

will run a functional test for approximately 3 seconds. During this test, four dots will appear in<br />

each of the two display fields. Once the test has been successfully completed, the dots will<br />

disappear, indicating that the RT60 is ready for operation.<br />

1 “OFF” will appear in the upper display field.<br />

Actuate the ON/OFF key.<br />

The set-point temperature, SP, will appear in the lower display field and the actual temperature<br />

of the internal sensor, S1, in the upper display field.<br />

For other possible messages, please see Section 2.8 and the RT Operating Instructions.<br />

2 Enter the desired set-point value using the keys. To set other values, please refer to the<br />

RT60 Operating Instructions.<br />

3 Check the temperature control circuit for leakage.<br />

4 Once water flows out of it regularly, close the consumer vent valve.<br />

Any component in contact with hot water.<br />

05 / 2005 9


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

2.7 Operating modes<br />

– Pressure mode Normal operation. Heat transfer medium is forced through the consumer.<br />

– Leak-stop mode Heat transfer medium is moved through the consumer by means of suction.<br />

Reduced pump capacity.<br />

– Suction Evacuation of the heat transfer fluid from the consumer by means of suction.<br />

mportant: Note maximum expansion volume ( Technical data).<br />

2.7.1 Leak-stop mode and evacuation of the consumer by means of suction<br />

The heat transfer fluid is vacuumed through the consumer by reversing the pump’s direction of<br />

rotation.<br />

2.7.1.1 Leak-stop mode<br />

With the unit in normal mode or switched off, the unit can be switched to leak-stop mode by pressing<br />

the LEAK STOP key. During leak-stop mode, the LEAK STOP LED will be lit.<br />

To interrupt leak-stop mode, press the ON/OFF key.<br />

To return to normal operation, wait until the LEAK STOP LED has gone out, then press the ON/OFF<br />

key once more.<br />

2.7.1.2 Suction mode<br />

To initiate the suction program, press the SUCTION key. The factory setting for suction mode is 60<br />

seconds. The consumer connected to the unit will be evacuated. During suction mode, the<br />

SUCTION LED will be lit.<br />

To interrupt the suction program, press the ON/OFF key.<br />

Suction is possible only when the temperature of the medium, S1, is below the programmed pump<br />

run-out temperature, P.tE. (factory setting 80 °C). If the medium is above this temperature, the unit<br />

will first cool to this value.<br />

The suction program can also be run once after the unit has been switched off using the ON/OFF<br />

key (display reads “OFF”).<br />

To return to normal operation, wait until the SUCTION LED has gone out, then press the ON/OFF<br />

key once more.<br />

10<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

2.8 Operating displays<br />

Switch-on phase. Automatic<br />

functional test runs for approx. 3<br />

sec. During the test, four dots<br />

appear in each of the display<br />

fields.<br />

Control off<br />

RT60 in standby mode.<br />

Display of actual and set-point<br />

values. Control on using the ON<br />

key.<br />

E.g.: Actual value 148.8 °C, Setpoint<br />

value 150.0 °C.<br />

Display during analogue<br />

set-point input. The set<br />

point can be retrieved<br />

using the keys.<br />

Display during interface<br />

operation. The unit’s address is<br />

shown in the lower display field.<br />

E.g.: A.13. The set point can be<br />

retrieved using the keys.<br />

ON/OFF key. Continuous LED: Unit in operation. Blinking LED: Pump run-out active<br />

(factory setting 80 °C).<br />

LEAK STOP key. Leak-stop mode activated when LED lit.<br />

SUCTION key. Suction program activated when LED lit (factory setting 60 sec.).<br />

ALARM RESET key. Alarm activated when LED lit.<br />

05 / 2005 11


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

2.9 Menu overview<br />

Actual value display<br />

Control parameter selection<br />

Sensor input settings<br />

Group-interrupt relay settings<br />

1 / 2 relay function<br />

Unit configuration<br />

Level settings<br />

Special control-parameter settings<br />

Operating hours, factory settings<br />

Analogue inputs and outputs<br />

Serial interface<br />

Parameter code input<br />

12<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

3 Malfunctions<br />

Before correcting any malfunctions, switch off the unit, actuate the main<br />

power switch and unplug the power cord.<br />

3.1 Alarm messages<br />

Messages alternate with the current display.<br />

Display Cause Correction<br />

Sensor break or short circuit. Cooling is<br />

switched on<br />

Check sensor connection.<br />

Replace sensor<br />

Level alarm<br />

Refill heat-transfer fluid<br />

Maximum pump current exceeded.<br />

Electromechanical safety thermostat triggered.<br />

Cooling is switched on<br />

Check pump for corrosion.<br />

Check motor<br />

Reset safety thermostat<br />

Temperature control unit’s selected maximum<br />

set point exceeded at sensor S1<br />

Cooling is switched on<br />

Programmed upper limit value exceeded<br />

Programmed lower limit value undershot<br />

Incorrect phase sequence at mains input.<br />

Appears after switching on using ON/OFF key<br />

Missing phase at mains connection. Appears<br />

after switching unit on<br />

Option "analogue I/O": External set point outside<br />

of set range<br />

Short circuit at a 24 V output<br />

Set-point/actual value for leak-stop mode too<br />

high.<br />

Switch two phases at mains input<br />

Check incoming mains cable and<br />

back-up fuse<br />

Check scaling and values at<br />

analogue input<br />

Check valve solenoid, valve plug (if<br />

present)<br />

Correct set point.<br />

05 / 2005 13


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

Display Cause Correction<br />

Electromechanical safety thermostat defective.<br />

(If present: Temperature set at heater auxiliary<br />

thermostat exceeded). Cooling is switched on.<br />

Minimum pump current less than 0.2 A. Mains<br />

input phase failed. Motor running on two phases.<br />

Check incoming mains cable, backup<br />

fuse and motor.<br />

Analogue/digital converter defective.<br />

Replace entire controller.<br />

Microprocessor ROM defective.<br />

Replace entire controller.<br />

Microprocessor RAM defective.<br />

Replace entire controller.<br />

Incorrect calibration value for sensor, pump<br />

current.<br />

Replace entire controller.<br />

Incorrect unit data in memory.<br />

Appears for 3 sec. after dAtA Err. is<br />

acknowledged. (Does not blink.)<br />

Mains voltage below 340 V.<br />

Reset by pressing ALARM RESET<br />

key. Default settings will be loaded.<br />

Try to reset the factory settings. If<br />

this does not work, replace the entire<br />

controller<br />

Check mains supply.<br />

No factory settings saved.<br />

Replace entire controller.<br />

Maintenance/Service due. (Does not blink.)<br />

Factory setting 2000 h. Message disappears<br />

when the unit is switched on via the ON/OFF<br />

key, but reappears as soon as the unit is<br />

switched off again.<br />

After service 4 I, enter the number<br />

of operating hours until next<br />

maintenance/service.<br />

Incorrect code entered.<br />

Correct using<br />

key.<br />

14<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

3.2 Switching the unit off<br />

3.2.1 By pressing the ON/OFF key<br />

The switch-off program runs automatically as follows, in accordance with the temperature of the heat<br />

transfer fluid:<br />

1 All display messages and LEDs go blank, except for “OFF” in the upper display field. The pump<br />

and control are switched off. RT60 remains powered, in standby mode.<br />

2 The ON/OFF LED blinks while the pump continues to run. The unit cools until the heat transfer<br />

fluid reaches the programmed pump-run out temperature, P.tE. (factory setting 80 °C).<br />

3 The pump and control are switched off. The RT60 switches to standby mode.<br />

4 All displays except for “OFF” go blank.<br />

3.2.2 By previous evacuation of the consumer<br />

See Section 2.7.<br />

3.2.3 Changing the consumer. Shutting the unit down for longer than one month.<br />

Switching the unit back on.<br />

Before removing the connection hoses, ensure that the unit is switched off and that all circuits are<br />

free of pressure.<br />

The unit must be evacuated completely and stored in a dry location between 10 und 40 °C when not<br />

in use.<br />

Condensation can build up during storage; before switching the unit back on, proceed as described<br />

in Sections 4.8 and 2.6.2.<br />

Hot water escaping from the unit can cause injury!<br />

Before disconnecting the hoses in the temperature control circuit, cool<br />

the unit as needed (as determined by the outlet temperature) and then<br />

switch off. Ensure that the pump has stopped running.<br />

3.2.4 By previous evacuation of the consumer<br />

See Section 2.7.<br />

05 / 2005 15


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

4 Maintenance<br />

Switch off the unit before performing any maintenance procedures. Actuate<br />

the main switch and unplug the main power cord.<br />

4.1 Periodic checks and maintenance<br />

To simplify maintenance procedures, the RT60 control system is equipped with a service-interval<br />

display. We recommend entering the appropriate service interval (e.g. 2000 hours). For<br />

programming, RT 60 Operating Instructions, messages “SerU.” and “duE”.<br />

Please note that the following information is for a daily operating interval of 8 hours. When operating<br />

with more than one shift, these checks and maintenance procedures shall be performed in<br />

correspondingly shorter intervals. Defective components shall be repaired or replaced immediately.<br />

• Checks and maintenance procedures shall be performed by qualified personnel.<br />

• Maintenance procedures on the electrical equipment shall be performed by a qualified<br />

electrician.<br />

• Do not replace the RT60 control unit until the power cord has been unplugged.<br />

4.2 Daily checks/maintenance<br />

Check the temperature control circuit (unit, connecting hoses, consumer, etc.) for leaks. Repair any<br />

leaks immediately.<br />

4.3 Monthly checks/ maintenance<br />

1 Check the inlet opening for the pump cooling for blockage. Clean unit from the inside out using<br />

compressed air.<br />

2 Clean the filter.<br />

4.4 Semi-annual checks/maintenance<br />

1 Level control functional test: Evacuate the unit via the drain plug, then switch on as described in<br />

Section 2.6.2, under “Initial set-up”.<br />

2 Check electrical equipment such as grounding wires, RT60 plug, firm connection of power and<br />

other electrical cables, etc.<br />

3 Disassemble solenoid valve: Check diaphragm for scaling and damage. Ensure that the core and<br />

spring bolts move freely. Clean or replace components as needed.<br />

4 Descale cooler.<br />

16<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

4.5 Annual checks/maintenance<br />

Always replace the oil after approximately 2000 hours of operation (approximately one year of<br />

single-shift operation).<br />

Please note that this value is provided as a guideline only. Actual operating conditions (temperature,<br />

small consumer diameter, operation in primarily heating mode, etc.) may require more frequent<br />

replacement. ( 4.6).<br />

4.6 Replacing the heat transfer fluid<br />

Replace the heat transfer fluid as follows:<br />

1 Evacuate the unit and consumer completely via the corresponding drain<br />

plugs (1, Fig. 3).<br />

2 Depending upon the number of hours in operation, clean the unit and<br />

consumer ( Cleaning).<br />

3 Refill the unit ( 2.6.2 Initial set-up) and switch on.<br />

1<br />

Fig. 3: Drain plug<br />

4.7 Cleaning<br />

– Always cool the unit prior to cleaning.<br />

– Switch off the unit, actuate the main power switch and unplug<br />

the power cord.<br />

– Due to danger of explosion, rinse the tank and cooler when using<br />

solvents for cleaning; do not blow them out. Follow all manufacturer’s<br />

regulations when using solvents.<br />

– Solvents are flammable under certain conditions. Cleaning shall not be<br />

performed in the vicinity of heat sources.<br />

We recommend that the following cleaning procedures be performed each time the heat transfer<br />

fluid is added or replaced. Suboptimal operating conditions require that the procedures listed below<br />

be performed with greater frequency.<br />

05 / 2005 17


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

1 Evacuate the unit via the drain plugs (1, Fig. 3).<br />

2 Clean the circuit filter (when present).<br />

3 Disassemble the unit ( Repairs).<br />

4 Remove the tank cover and clean tank.<br />

5 Check the cooler for scaling; clean using MTA descaling agent as<br />

NO<br />

needed.<br />

6 Clean heating elements<br />

7 Level monitor: Remove and clean floater. Attention: Ensure that the<br />

floater is reinstalled properly<br />

(NO up, Fig. 4).<br />

8 Disassemble solenoid valve: Check diaphragm for scaling and damage.<br />

Fig. 4: Level switch<br />

Ensure that the core and spring bolts move freely. Clean or replace<br />

components as needed.<br />

9 Check pump for corrosion; replace as needed.<br />

10 We also recommend checking the consumer for lime deposits every time the unit<br />

is cleaned as well as cleaning it with the aid of the descaling unit MTA. As previously<br />

mentioned, rust and lime deposits drastically reduce the exchange of heat between<br />

the consumer and circulating fluid.<br />

Lime deposits also increase the pressure drop<br />

within the consumer, so that the pump capacity of the unit may no longer be sufficient<br />

to transfer the required amount of heat.<br />

18<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

5 Repairs<br />

Before performing any repairs:<br />

– Cool the unit.<br />

– Switch the unit off, actuate the main power switch and unplug the<br />

power cord.<br />

– Disconnect all hoses from the unit.<br />

To simplify and expedite repairs, the unit can be disassembled as follows:<br />

1 Remove side panel.<br />

2 Detach the control unit from the housing by removing the four screws. Attention: First disconnect<br />

all plugs.<br />

3 Remove filter.<br />

4 Detach the housing from the base by removing four screws and pull it off over the hydraulic<br />

connections from the rear. The tank unit is now free.<br />

5 Remove the pump and heater.<br />

6 Remove the tank cover by removing four screws.<br />

7 Remove the cooler and float switch.<br />

Reassemble by reversing the above procedure.<br />

Replacement parts and order forms Service.<br />

05 / 2005 19


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

6 Shipping<br />

– Cool the unit.<br />

– Switch the unit off, actuate the main power switch and unplug the<br />

power cord.<br />

– Disconnect all hoses from the unit.<br />

Before shipping, evacuate the unit completely via the drain.<br />

1 Switch the unit on: Actuate the main power switch and press the ON key.<br />

2 Set the set-point value at the controller to 0 °C.<br />

3 Ensure that the Cooling LED is lit, i.e. the cooling solenoid valve is open.<br />

4 At low temperatures, to avoid damage due to freezing (cooling hose collapse), blow out with<br />

compressed air at a maximum pressure of 6 bar.<br />

5 Switch the unit off using the OFF/OFF key, actuate the main power switch and unplug the power<br />

cord.<br />

6 Do not tip the unit.<br />

7 Use the original packing material.<br />

8 Follow any instructions on the packing material.<br />

7 Spare parts Spate<br />

Use only genuine spare parts.<br />

To ensure efficient ordering of replacement parts and to avoid errors, we need the details below.<br />

1 Unit type<br />

2 Serial number<br />

3 Voltage<br />

4 Frequency<br />

5 Item number of the part<br />

20<br />

05 / 2005


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

35 - M10<br />

A1<br />

A1 – F1-4<br />

Q1<br />

F5<br />

E2<br />

S3 – B1<br />

38<br />

9<br />

30<br />

72<br />

67<br />

73<br />

66<br />

70<br />

43<br />

60<br />

54<br />

41<br />

75<br />

Y6<br />

Y2a<br />

Y1<br />

43<br />

05 / 2005 21


<strong>MOTEMP</strong> S <strong>90</strong> <strong>WL</strong><br />

Pos. Item Part no.<br />

9 Castor with wheel brake 460-100016<br />

35 Pump with outlet pipe TP20 380-420V/50 Hz 322-100018<br />

38 Tank 371-100012<br />

Insulation 440-100012<br />

41 Cooler 440-100000<br />

43 Valve-block without coils 350-100016<br />

54 Tank lid, Set of seals tank/pump/heater 340-100005<br />

60 Filter cooling water 3/8" 352-100008<br />

Strainer 352-100016<br />

68 Deckel zu Ablass-Stutzen 300-070160<br />

Dichtung ∅ 15x2 340-070302<br />

75 Castor 460-100015<br />

A1 Control unit with main switch 163-100005<br />

E21 Heater with safety thermostat 311-100007<br />

F5 Safety thermostat 150-10000<br />

F1-3 Fuse FF 16 A H 143-100011<br />

F4 Fuse T 1.6 A L 143-100010<br />

S3 Level switch with sensor Pt100 154-100008<br />

Y2a Automatic water refillmagnet control part 350-100022<br />

Y6a Cooling magnet control part 350-100022<br />

Y6d Diaphragm 350-100012<br />

Y6a Draining magnet control part 350-100022<br />

Y2c-6c<br />

13c<br />

Assembly with 3 coils 350-100023<br />

22<br />

05 / 2005

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!