The user-defined program is stored and executed in the central unit (CU).<br />

The LED’s provide information about the current operation status (error, mode of operation, status of in-/outputs, communication and datalogger)<br />

of the system. Facility- and system data are saved event-triggerd on the MultiMediaCard TM (MMC TM ) by the usage of the datalogger.<br />

The operation mode can be chosen by the use of the mode selector with following settings:<br />

RRun<br />

RStop<br />

Run<br />

Stop<br />

Remote Run (program runs after reset, access of the programming environment to the Central unit is possible)<br />

Remote Stop (program doesn‘t run after reset, access of the programming environment to the Central unit is possible)<br />

Program runs after reset, access of the programming environment to the Central unit is only possible to a limited degree,<br />

communication with modem<br />

Program doesn‘t run after reset, access of the programming environment to the CU is only possible to a limited degree<br />

The firmware and applications can be updated via the software. The firmware and application update can also be performed by means of<br />

the MultiMediaCard TM .<br />

Functions<br />

Connections<br />

WatchDog pro<br />

Voltage monitoring in 1-phase mains<br />

< Voltage measurement in 1-phase mains<br />

< Measured range 10V for standard signal (G2UI1 10V)<br />

< Measuring ranges for 30V, 60V and 300V (G2UI1 300V)<br />

< Measuring ranges 60mV and 150mV for shunt measurement (G2UI1 10V)<br />

< Reinforced insulation of the measuring circuit<br />

< Measured value transmitting via standard bus<br />

< Modular monitoring system<br />

< Width 22,5mm<br />

< Industrial design<br />

Digital inputs:<br />

DIGND +24V ... 100V DC / 24 ... 230V AC<br />

Type G2UI1 10V G2UI1 300V<br />

Optional serial interface:<br />

PC: GND RXD TXD<br />

DI<br />

DI3<br />

DI4<br />

13<br />

14<br />

DI1 DI2 SG STX SRX<br />

RB<br />

RB+ RBA RBB<br />

Supply:<br />

GND<br />

24V<br />

23<br />

24<br />

Art.No. (PQ1) 2500050 2500051<br />

GND<br />

24V DC<br />

Art.No. (PQ10) - -<br />

remote bus:<br />

GND A B<br />

EAN13-Code 900866200523 900866200488<br />

Width 45mm<br />

Dimensions<br />

Measured variable<br />

Measured ranges<br />

Voltage AC/DC<br />

DC or AC Sinus (16,6 to 400Hz)<br />

60mV AC/DC; terminals E-F1(+)<br />

150mV AC/DC; terminals E-F2(+)<br />

10V AC/DC; terminals E-F3(+)<br />

Voltage AC/DC<br />

DC or AC Sinus (16,6 to 400Hz)<br />

30V AC/DC; terminals E-F1(+)<br />

60V AC/DC; terminals E-F2(+)<br />

300V AC/DC; terminals E-F3(+)<br />

Controls<br />

Address adjustment:<br />

Address range 1 to 99<br />

Address adjustment:<br />

Address range 1 to 99<br />

7<br />

45<br />

Indicators (LEDs) U • Err • Com U • Err • Com<br />

Businterface Standard bus (RS485) Standard bus (RS485)<br />

Overvoltage cat. III (in accordance with IEC 60664-1) III (in accordance with IEC 60664-1)<br />

Rated surge voltage 6kV 6kV<br />

Supply 24V DC from local interface 24V DC from local interface<br />

Output - -<br />

Width 22,5mm 22,5mm<br />

Certificates CE • GOST CE • GOST<br />

Mechanical<br />

Design<br />

Self-extinguishing plastic housing, IP rating IP20 • Mounted on DIN-rail TS 35 in accordance with EN 60715 • Mounting position: any •<br />

Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque: max. 1Nm<br />

Accessories<br />

G4NG230V24V2.5A Power supply, 230VAC, 24VDC/2,5A, 1-phase 2600000<br />

WDP SOFT<br />

Parameterisation software<br />

2500030<br />

Programming environment on CD, running on Windows 98/ME/2000/XP<br />

MMC-READER<br />

MMC read out package<br />

including Datenlogger software and MMC Card Reader<br />

2500035<br />

Terminal capacity<br />

Ambient<br />

conditions<br />

Accessories -<br />

1 x 0.5 to 2.5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0.5 to 1.5mm² with/without multicore cable end<br />

• 2 x 2.5mm² flexible without multicore cable end<br />

Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1); -25 to +40°C (in accordance with UL 508) • Storage temperature: -25<br />

to +70°C • Transport temperature: -25 to +70°C • Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Absolute<br />

humidity: 1g to 25g H 2<br />

O/m 3 (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2 (in accordance with IEC 60664-1) • Vibration<br />

resistance: 10 to 55Hz 0.35mm (in accordance with IEC 60068-2-6) • Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27)<br />

WDP COM<br />

Communication equipment WatchDog pro<br />

including USB serial converter and interface cable RS232<br />

2500040<br />

WDP GSM Datacenter WatchDog pro GSM Datensolotion for the two-way communication 2500046<br />

WDP GPRS Datacenter WatchDog pro GPRS Datensolotion for the two-way communication 2500048<br />

WDP GSM WatchDog pro GSM Package for the simple report of informations via SMS 2500045<br />

MMC 1GB MultiMediaCard 1GB (formated memorycard) 2500010<br />

MMC 2GB MultiMediaCard 2GB (formated memorycard) 2500020<br />

STANDARD CABLE HMI/WDP RS485 5M RS485 Standard connecting cable WDP/Touchpanel, display type LCD/STN/TFT 2500894<br />

Page 164<br />

www.tele-online.com Page 165