WatchDog pro<br />

Central Unit<br />

< Information about the operating status (error, operation mode, status of<br />

In- and outputs, communication and datalogger)<br />

< Selectable operation mode<br />

< Recording of facility- and system data via MultiMediaCard TM (MMC TM )<br />

< Reinforced insulation of the input and output circuit<br />

< 4 digital inputs<br />

< 2 relay outputs<br />

< Width 45mm<br />

< Industrial design<br />

Type<br />

G4WDCU MMC<br />

Art.No. (PQ1) 2500000<br />

Art.No. (PQ10) -<br />

EAN13-Code 900866200329<br />

Input circuit<br />

Digital inputs<br />

Internal values<br />

Controls<br />

Indicators (LEDs)<br />

Datalogger<br />

Businterface<br />

Communication<br />

Voltage AC/DC<br />

AC Sinus (48 to 63Hz)<br />

24 to 230V AC • 24 to 100V DC (input activ)<br />

Device temperature • Current remote bus • Current local interface •<br />

Supply voltage • Battery voltage<br />

RRun • RStop • Run • Stop<br />

U • U ERR<br />

• Temp • I RB/LI<br />

• Err • Remote • RUN • STOP • Modem • DI1 • DI2 • DI3 • DI4 • R1 • R2 • ready • busy • RS232 • HCom • Com<br />

MMC<br />

Standard bus (RS485)<br />

RS232 with PC • Modem<br />

Remote bus RS485 over RB , (RB+), RBA, RBB<br />

Overvoltage cat. III (in accordance with IEC 60664-1)<br />

Rated surge voltage<br />

Permanent registers<br />

Registers max. 845<br />

Supply<br />

Output<br />

Width<br />

Certificates<br />

Mechanical<br />

design<br />

Terminal capacity<br />

Ambient<br />

conditions<br />

Accessories<br />

6kV<br />

27 and 128 permanent boolean registers<br />

24VDC<br />

2 NO contacts<br />

250V AC, 3A AC<br />

45mm<br />

CE • GOST<br />

Self-extinguishing plastic housing, IP rating IP20 • Mounted on DIN-rail TS 35 in accordance with EN 60715 • Mounting position: any •<br />

Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque: max. 1Nm<br />

1 x 0.5 to 2.5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0.5 to 1.5mm² with/without multicore cable end<br />

• 2 x 2.5mm² flexible without multicore cable end<br />

Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1); -25 to +40°C (in accordance with UL 508) • Storage temperature: -25<br />

to +70°C • Transport temperature: -25 to +70°C • Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Absolute<br />

humidity: 1g to 25g H 2<br />

O/m 3 (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2 (in accordance with IEC 60664-1) • Vibration<br />

resistance: 10 to 55Hz 0.35mm (in accordance with IEC 60068-2-6) • Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27)<br />

WDP SOFT • WDP COM • WDP GSM • MMC Card<br />