catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Zero<br />
setting of zero point (0%, 25%, 50%, 75% of nominal value)<br />
Functions<br />
Zero Fine<br />
fine setting of zero point (0% ... 25% of nominal value)<br />
Span<br />
span (100%, 75%, 50%, 25% of nominal value)<br />
Range<br />
measuring range reversible between 5A, 10A, 15A<br />
G2IA15A 4...20mA in 3-phase mains G2IA15A 4...20mA in 3-phase mains with current transformer Connections<br />
Loadmonitors Series GAMMA<br />
Power factor monitoring (cosj) in 1- or 3-phase mains<br />
< Multifunction (G2CM)<br />
< Underload monitoring (G2CU)<br />
< Fault latch<br />
< Recognition of disconnected consumers I=0<br />
< Suitable for VFI (10 to 100Hz)<br />
< Supply voltage selectable via PowerModules<br />
< 2 CO contacts (G2CM); 1 CO contact (G2CU)<br />
< Width 22,5mm<br />
< Industrial design<br />
L<br />
N<br />
L1<br />
N<br />
types G2CM400V10AL20 G2CM400V2AL20 G2CU400V10AL10<br />
i k A1<br />
i k A1<br />
X1 X2 A2<br />
X1 X2 A2<br />
Art.No. (PQ1) 2390602 2390606 2390600<br />
Last<br />
4...20mA<br />
Last<br />
4...20mA<br />
Art.No. (PQ10) - - -<br />
EAN13-Code 900866200289 900866200290 900866200288<br />
Width 22,5mm<br />
Dimensions<br />
Measured variable<br />
Power factor (cosj) of<br />
1- or 3-phase loads<br />
AC Sinus (10 to 100Hz)<br />
Power factor (cosj) of<br />
1- or 3-phase loads<br />
AC Sinus (10 to 100Hz)<br />
Power factor (cosj) of<br />
1- or 3-phase loads<br />
AC Sinus (10 to 100Hz)<br />
Measured range 0,1 to 1 0,1 to 1 0,1 to 1<br />
Measuring voltage<br />
1-phase loads: 40 to 240VAC<br />
3-phase loads: 3~ 40/23 to 415/240V<br />
1-phase loads: 40 to 240VAC<br />
3-phase loads: 3~ 40/23 to 415/240V<br />
1-phase loads: 40 to 240VAC<br />
3-phase loads: 3~ 40/23 to 415/240V<br />
Rated current 0,5 to 10A 0,05 to 2A 0,5 to 10A<br />
Controls Start • max • min • Delay • Function Start • max • min • Delay • Function Start • min • Delay • Function<br />
Indicators (LEDs) U/t • min • max • I=0 • R U/t • min • max • I=0 • R U/t • min • I=0 • R<br />
Functions<br />
OVER<br />
OVER+LATCH<br />
UNDER<br />
UNDER+LATCH<br />
WIN<br />
WIN+LATCH<br />
OVER<br />
OVER+LATCH<br />
UNDER<br />
UNDER+LATCH<br />
WIN<br />
WIN+LATCH<br />
UNDER<br />
UNDER+LATCH<br />
Switching threshold max. cosj = 0,2 to 1,0 cosj = 0,2 to 1,0 -<br />
Switching threshold min. cosj = 0,1 to 0,99 cosj = 0,1 to 0,99 cosj = 0,1 to 1,0<br />
Hysteresis - - fixed, approx. 3°<br />
(according to 3% bei cosj=0,8)<br />
Tripping delay 0,1s to 40s 0,1s to 40s 0,1s to 40s<br />
Start-up suppression time 1s to 100s 1s to 100s 1s to 100s<br />
Fault latch selectable selectable selectable<br />
Supply<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
Output 2 CO contacts; 250V, 5A AC 2 CO contacts; 250V, 5A AC 1 CO contact; 250V, 5A AC<br />
Width 22,5mm 22,5mm 22,5mm<br />
Certificates CE • cULus • GOST CE • cULus • GOST CE • cULus • GOST<br />
Mechanical<br />
design<br />
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position any •<br />
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm<br />
Terminal capacity<br />
1 x 0,5 to 2,5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />
• 2 x 2,5mm² flexible without multicore cable end<br />
Ambient<br />
conditions<br />
Ambient temperature: -25 to 55°C (in accordance with IEC 60068-1); -25 to 40°C (in accordance with UL 508) • Storage temperature: -25 to<br />
+70°C • Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree:<br />
3 (in accordance with IEC 60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (in accordance with IEC 60068-2-6) • Shock resistance: 15g<br />
11ms (in accordance with IEC 60068-2-27)<br />
Accessories<br />
PowerModules TR2 (12 - 440V AC) and DC power supply SNT2 24 VDC • sealable intervention protection shield FA-G2<br />
Page 100 www.tele-online.com<br />