catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
OVP1<br />
Automatic (AUTO): The contact of checkback B1-B2 is closed. The input signal applied to terminal YR is looped through unchanged to<br />
terminal Y.<br />
Permanently OFF (0): The contact of checkback B1-B2 is opened. No outputsignal at terminal Y.<br />
Manual signal (HAND): The contact of checkback B1-B2 is opened. Output signal at terminal Y (0 to 10V DC) according to the value set<br />
on the front mounted regulator.<br />
OCP1<br />
Automatic (AUTO): The contact of checkback B1-B2 is closed. The input signal applied to terminal YR is looped through unchanged to<br />
terminal Y.<br />
Permanently OFF (0): The contact of checkback B1-B2 is opened. No outputsignal at terminal Y.<br />
Manual signal (HAND): The contact of checkback B1-B2 is opened. Output signal at terminal Y (0 to 20mA DC) according to the value set<br />
on the front mounted regulator.<br />
Functions<br />
Coupling units Series OCTO<br />
Levelswitch<br />
< Trigger 1 to 10V DC (OVL1)<br />
< Trigger 2 to 20mA DC (OCL1)<br />
< Checkback signal for switch setting AUTO<br />
< 1 CO contact<br />
< Width 17,5mm<br />
< Installation design<br />
OVP1 OCP1 Connections<br />
24V<br />
0V<br />
0-10V<br />
24V<br />
0V<br />
0-20mA<br />
Type OVL1 24VAC/DC OCL1 24VAC/DC<br />
A1<br />
A2<br />
A1<br />
A2<br />
B1<br />
B2<br />
B1<br />
B2<br />
YR Y<br />
Potentiometer<br />
Output<br />
0-10V<br />
YR Y<br />
Potentiometer<br />
output signal<br />
0-20mA<br />
GND<br />
YR<br />
GND<br />
YR<br />
GND<br />
Y<br />
GND<br />
Y<br />
Art.No. (PQ1) 170015 170017<br />
Art.No. (PQ10) - -<br />
EAN13-Code 900866200072 900866200074<br />
Controls Function • levelswitch Function • levelswitch<br />
Width 17,5mm<br />
Dimensions<br />
Indicators (LEDs) U • R U • R<br />
Functions<br />
AUTO (output according to signal on YR)<br />
0 (permanently OFF)<br />
1 (permanently ON)<br />
AUTO (output according to signal on YR)<br />
0 (permanently OFF)<br />
1 (permanently ON)<br />
Trigger level 1 to 10V DC 2 to 20mA DC<br />
Analogue input<br />
Checkback<br />
Supply<br />
Output<br />
input for automatic operation<br />
0 to 10V DC<br />
terminals YR-A2<br />
1 potential free NO contact for checkback signal of the switch setting<br />
AUTO<br />
28V AC/DC; 2A<br />
terminals B1-B2<br />
24V AC/DC<br />
terminals A1-A2<br />
1 potential free CO contact<br />
250V AC, 8A<br />
input for automatic operation<br />
0 to 20mA DC<br />
terminals YR-A2<br />
1 potential free NO contact for checkback signal of the switch setting<br />
AUTO<br />
28V AC/DC; 2A<br />
terminals B1-B2<br />
24V AC/DC<br />
terminals A1-A2<br />
1 potential free CO contact<br />
250V AC, 8A<br />
Width 17,5mm 17,5mm<br />
Certificates CE • GOST CE • GOST<br />
Mechanical<br />
design<br />
Terminal capacity<br />
Ambient<br />
conditions<br />
Accessories -<br />
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position any •<br />
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm<br />
1 x 0,5 to 2,5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />
• 2 x 2,5mm² flexible without multicore cable end<br />
Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to<br />
+70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2, if built in 3 (in accordance with IEC<br />
60664-1)<br />
Page 230 www.tele-online.com<br />
Page 231