18.01.2015 Views

catalog TELE - CONTA-CLIP

catalog TELE - CONTA-CLIP

catalog TELE - CONTA-CLIP

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Automatic (AUTO)<br />

The contact of checkback B1-B2 is closed.<br />

When the signal voltage U is applied at terminal A3 the output relay R switches into on-position (yellow LD illuminated)<br />

Permanently OFF (0)<br />

The contact of checkback B1-B2 is opened.<br />

The output relay R remains in off-position independent from the connected signal voltage.<br />

Permanently ON (HAND)<br />

The contact of checkback B1-B2 is opened.<br />

When the supply voltage U is applied at terminal A1 the output relay R switches into on-position (yellow LED illuminated). Changes of the<br />

signal voltage do not influence the state of the output relay.<br />

Functions<br />

Coupling units Series OCTO<br />

Analogue data encoder<br />

< Analogue data encoder 0 to 10V DC (OVP1)<br />

< Analogue data encoder 0 to 20mA DC (OCP1)<br />

< Checkback signal of the switch setting AUTO<br />

< 1 analogue output and 1 NO contact (checkback)<br />

< Width 17,5mm<br />

< Installation design<br />

HAR1<br />

Connections<br />

Supply voltage (+)<br />

Signal voltage (+)<br />

Type OVP1 24VAC/DC OCP1 24VAC/DC<br />

Checkback<br />

AUTO<br />

A1<br />

B1<br />

A2<br />

B2<br />

11<br />

12 14<br />

Width 17,5mm<br />

11<br />

12<br />

A3<br />

14<br />

Dimensions<br />

Art.No. (PQ1) 170012 170018<br />

Art.No. (PQ10) - -<br />

EAN13-Code 900866200069 900866200075<br />

Controls function • analogue data function • analogue data<br />

Indicators (LEDs) LED (intensity according to the value of the output signal) LED (intensity according to the value of the output signal)<br />

Functions<br />

Analogue input<br />

Output<br />

Checkback<br />

Supply<br />

AUTO (output according to input YR)<br />

0 (permanently OFF)<br />

HAND (output according to set value (regulator)<br />

input for automatic operation<br />

0 to 10V DC<br />

terminals YR-GND<br />

1 analogue output<br />

0 to 10V DC<br />

terminals Y-GND<br />

1 potential free NO contact for checkback signal of the switch setting<br />

AUTO<br />

28V AC/DC; 2A<br />

terminals B1-B2<br />

24V AC/DC<br />

terminals A1-A2<br />

AUTO (output according to input YR)<br />

0 (permanently OFF)<br />

HAND (output according to set value (regulator)<br />

input for automatic operation<br />

0 to 20mA DC<br />

terminals YR-GND<br />

1 analogue output<br />

0 to 20mA DC<br />

terminals Y-GND<br />

1 potential free NO contact for checkback signal of the switch setting<br />

AUTO<br />

28V AC/DC; 2A<br />

terminals B1-B2<br />

24V AC/DC<br />

terminals A1-A2<br />

Width 17,5mm 17,5mm<br />

Certificates CE • GOST CE • GOST<br />

Mechanical<br />

design<br />

Terminal capacity<br />

Ambient<br />

conditions<br />

Accessories -<br />

Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position any •<br />

Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm<br />

1 x 0,5 to 2,5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />

• 2 x 2,5mm² flexible without multicore cable end<br />

Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to<br />

+70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2, if built in 3 (in accordance with IEC<br />

60664-1)<br />

Page 228 www.tele-online.com<br />