Automatic (AUTO)<br />
The contact of checkback B1-B2 is closed.<br />
When the signal voltage U is applied at terminal A3 the output relay R switches into on-position (yellow LD illuminated)<br />
Permanently OFF (0)<br />
The contact of checkback B1-B2 is opened.<br />
The output relay R remains in off-position independent from the connected signal voltage.<br />
Permanently ON (HAND)<br />
The contact of checkback B1-B2 is opened.<br />
When the supply voltage U is applied at terminal A1 the output relay R switches into on-position (yellow LED illuminated). Changes of the<br />
signal voltage do not influence the state of the output relay.<br />
Functions<br />
Coupling units Series OCTO<br />
Analogue data encoder<br />
< Analogue data encoder 0 to 10V DC (OVP1)<br />
< Analogue data encoder 0 to 20mA DC (OCP1)<br />
< Checkback signal of the switch setting AUTO<br />
< 1 analogue output and 1 NO contact (checkback)<br />
< Width 17,5mm<br />
< Installation design<br />
HAR1<br />
Connections<br />
Supply voltage (+)<br />
Signal voltage (+)<br />
Type OVP1 24VAC/DC OCP1 24VAC/DC<br />
Checkback<br />
AUTO<br />
A1<br />
B1<br />
A2<br />
B2<br />
11<br />
12 14<br />
Width 17,5mm<br />
11<br />
12<br />
A3<br />
14<br />
Dimensions<br />
Art.No. (PQ1) 170012 170018<br />
Art.No. (PQ10) - -<br />
EAN13-Code 900866200069 900866200075<br />
Controls function • analogue data function • analogue data<br />
Indicators (LEDs) LED (intensity according to the value of the output signal) LED (intensity according to the value of the output signal)<br />
Functions<br />
Analogue input<br />
Output<br />
Checkback<br />
Supply<br />
AUTO (output according to input YR)<br />
0 (permanently OFF)<br />
HAND (output according to set value (regulator)<br />
input for automatic operation<br />
0 to 10V DC<br />
terminals YR-GND<br />
1 analogue output<br />
0 to 10V DC<br />
terminals Y-GND<br />
1 potential free NO contact for checkback signal of the switch setting<br />
AUTO<br />
28V AC/DC; 2A<br />
terminals B1-B2<br />
24V AC/DC<br />
terminals A1-A2<br />
AUTO (output according to input YR)<br />
0 (permanently OFF)<br />
HAND (output according to set value (regulator)<br />
input for automatic operation<br />
0 to 20mA DC<br />
terminals YR-GND<br />
1 analogue output<br />
0 to 20mA DC<br />
terminals Y-GND<br />
1 potential free NO contact for checkback signal of the switch setting<br />
AUTO<br />
28V AC/DC; 2A<br />
terminals B1-B2<br />
24V AC/DC<br />
terminals A1-A2<br />
Width 17,5mm 17,5mm<br />
Certificates CE • GOST CE • GOST<br />
Mechanical<br />
design<br />
Terminal capacity<br />
Ambient<br />
conditions<br />
Accessories -<br />
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position any •<br />
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque max. 1Nm<br />
1 x 0,5 to 2,5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />
• 2 x 2,5mm² flexible without multicore cable end<br />
Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to<br />
+70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2, if built in 3 (in accordance with IEC<br />
60664-1)<br />