ECO - How it works<br />
In most residential as well as in commercial buildings, the operation of some devices might be disabeled a few minutes without<br />
inconvenience of comfort and functionality. Eco takes advantage of this by disconnecting „loads“ such as heating of rooms or hot water<br />
provision for short periodes. As soon as the consumer system being monitored is again drawing less power, users that had previously been<br />
disconnected are progressively reconnected and can continue operating.<br />
The overall result is a significantly more consistent power uptake by the entire monitored consuming system – the plant’s power<br />
requirement is reduced.<br />
Functions<br />
Sequence processor Series STEP-T8<br />
State machine<br />
< Sequence processor with 4x20 programm steps<br />
< Function of control inputs programmable<br />
< 7 operation modes<br />
< Remanent latch function (selectable)<br />
< 8 NO contact<br />
< 1 CO contact<br />
< Width 157,5mm<br />
< Installation design<br />
Control inputs Connections Connections<br />
Power pulse of<br />
an energy meter<br />
Synchronisation impulse<br />
Tariff change-over<br />
Synchronisation<br />
of the real time clock<br />
Disconnection<br />
all load<br />
24V direct current supply<br />
Ground<br />
RS485 interface (A=RS485+)<br />
RS485 interface (B=RS485-)<br />
RS485 interface (A=RS485+)<br />
RS485 interface (B=RS485-)<br />
Type STEP-T8 110VAC STEP-T8 230VAC<br />
28 29 30 31 32 33 34 35 36 37<br />
PWR SYNC TAR CLK MOFF<br />
49 50 51 52 53 54<br />
A B A B<br />
24V<br />
GND<br />
Art.No. (PQ1) 454002 454001<br />
Art.No. (PQ10) - -<br />
EAN13-Code 900866200365 900866200364<br />
Controls 4 button programming 4 button programming<br />
Outputs<br />
Connections<br />
Indicators (LEDs) Display • 8 LEDs for output status • AL/SYNC • Power Display • 8 LEDs for output status • AL/SYNC • Power<br />
Regelausgänge<br />
Sammelstörmeldung<br />
Functions<br />
Sequence processor with 4x20 programm steps<br />
7 operation modes selectable:<br />
MODE 0 (standard - factory default) • MODE 1 (power failure detection)<br />
• MODE 2 (start requirement) • MODE 3 (power failure detection and<br />
start requirement) • MODE 4 (standard with extended Stop-function) •<br />
MODE 5 (power failure detection with extended Stop-function) • MODE<br />
6 (start requirement with extended Stop-function) • MODE 7 (power<br />
failure detection and start requirement with extended Stop-function)<br />
Sequence processor with 4x20 programm steps<br />
7 operation modes selectable:<br />
MODE 0 (standard - factory default) • MODE 1 (power failure detection)<br />
• MODE 2 (start requirement) • MODE 3 (power failure detection and<br />
start requirement) • MODE 4 (standard with extended Stop-function) •<br />
MODE 5 (power failure detection with extended Stop-function) • MODE<br />
6 (start requirement with extended Stop-function) • MODE 7 (power<br />
failure detection and start requirement with extended Stop-function)<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
F<br />
8 9 10 11 12 13 14 15 16 17 18 19<br />
20<br />
time ranges<br />
0,1s to 59min 59,9sec (100ms resolution)<br />
1s to 99h 95min 59sec (1s resolution)<br />
0,1s to 59min 59,9sec (100ms resolution)<br />
1s to 99h 95min 59sec (1s resolution)<br />
factory default<br />
control input setting<br />
Control input I1: RESET<br />
Connected: galvanic separated; terminals 28-29<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
Control input I2: TRIGGER<br />
Connected: galvanic separated; terminals 30-31<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
Control input I3: STOP<br />
Connected: galvanic separated; terminals 32-33<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
Control input I1: RESET<br />
Connected: galvanic separated; terminals 28-29<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
Control input I2: TRIGGER<br />
Connected: galvanic separated; terminals 30-31<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
Control input I3: STOP<br />
Connected: galvanic separated; terminals 32-33<br />
Typ: S0 (DIN 43864); 15mA DC / 24V DC<br />
selectable Input functions RESTART / STEP BACK • MANUAL • PROGRAMME CHANCE RESTART / STEP BACK • MANUAL • PROGRAMME CHANCE<br />
Width 157,5mm<br />
Dimensions<br />
Supply<br />
110VAC<br />
terminals A1-A2<br />
230VAC<br />
terminals A1-A2<br />
Output<br />
8 potential free NO contact 230V AC, 3A<br />
1 potential free NC contact 230V AC, 3A<br />
8 potential free NO contact 230V AC, 3A<br />
1 potential free NC contact 230V AC, 3A<br />
Width 157,5mm 157,5mm<br />
Certificates CE CE<br />
Mechanical<br />
design<br />
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position: any • Shockproof<br />
terminal connection according to VBG 4, IP rating IP20 • Tightening torque max. 1Nm<br />
Terminal capacity<br />
1 x 0,5 to 2,5mm² with/without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />
Ambient<br />
conditions<br />
Ambient temperature: 0 to 50°C (in accordance with IEC 60068-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to +70°C •<br />
relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2, if built in 3 (in accordance with IEC 60664-1)<br />