7 Block OUTPUTS <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

Function description<br />

OUTPUTS PULSE/FREQUENCY OUTPUT (1...2) CONFIGURATION (FREQUENCY)<br />

OUTPUT SIGNAL<br />

(continued)<br />

In the operating status (flow present), the output signal level changes from 0 V to a<br />

positive voltage level.<br />

U (V)<br />

t<br />

A0001975<br />

Example for output configuration PASSIVE-POSITIVE:<br />

Output configuration with an external pull-down resistance.<br />

In the quiescent state (at zero flow), a positive voltage level is measured via the<br />

pull-down resistance.<br />

+ U<br />

max<br />

=30VDC<br />

U (V)<br />

m<br />

U (V)<br />

o<br />

t<br />

n<br />

p<br />

t<br />

m = Open collector<br />

n = Pull-Down-Resistance<br />

o = Transistor activation in “POSITIVE” quiescent state (at zero flow)<br />

p = Output signal level in quiescent state (at zero flow)<br />

A0004689<br />

In the operating status (flow present), the output signal level changes from a positive<br />

voltage level to 0 V.<br />

U (V)<br />

t<br />

A0001981<br />

Example for output configuration PASSIVE-NEGATIVE:<br />

Output configuration with an external pull-up resistance.<br />

In the quiescent state (at zero flow), the output signal level at the terminals is at a positive<br />

voltage level.<br />

+ U<br />

max<br />

=30VDC<br />

U (V)<br />

m<br />

n<br />

U (V)<br />

o<br />

t<br />

p<br />

t<br />

m = Open collector<br />

n = Pull-Up-Resistance<br />

o = Transistor activation in “NEGATIVE” quiescent state (at zero flow)<br />

p = Output signal level in quiescent state (at zero flow)<br />

A0004690<br />

In the operating status (flow present), the output signal level changes from a positive<br />

voltage level to 0 V.<br />

U (V)<br />

(continued on next page)<br />

t<br />

A0001981<br />

Page 82 • MN0M023<br />

Issue/Rev. 0.2 (12/12)