<strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

7 Block OUTPUTS<br />

Function description<br />

OUTPUTS PULSE/FREQUENCY OUTPUT (1...2) CONFIGURATION (FREQUENCY)<br />

MEASURING MODE<br />

(4206) ! Note!<br />

This function is not available unless the FREQUENCY setting was selected in the<br />

OPERATION MODE function (4200).<br />

Use this function to define the measuring mode for the frequency output.<br />

Options:<br />

STANDARD<br />

SYMMETRY<br />

PULSATING FLOW<br />

Factory setting:<br />

STANDARD<br />

<strong>Description</strong> <strong>of</strong> the individual options:<br />

•STANDARD<br />

The frequency output signal is proportional to the measured variable. The flow<br />

components outside the scaled measuring range (defined by the VALUE F LOW m and<br />

the VALUE F HIGH n) are not taken into account for signal output.<br />

– If one <strong>of</strong> the values is defined as equal to the zero flow (e.g. VALUE F LOW =<br />

0 kg/h), no message is given if this value is exceeded or not achieved and the<br />

frequency output retains its value ( 0 Hz in the example). If the other value is<br />

exceeded or not achieved, the message “FREQUENCY OUTPUT AT FULL SCALE<br />

VALUE” appears and the frequency output responds in accordance with the<br />

parameter setting in the function FAILSAFE MODE (4209).<br />

– If both values defined are not equal to the zero flow (for example VALUE F LOW =<br />

–5 kg/h; VALUE F HIGH = 10 kg/h), the message “FREQUENCY OUTPUT AT<br />

FULL SCALE VALUE” appears if the measuring range is exceeded or not achieved<br />

and the frequency output responds in accordance with the parameter settings in the<br />

function FAILSAFE MODE (4209)...<br />

Freq.<br />

125<br />

100<br />

0<br />

➀<br />

➁<br />

Q<br />

A0001279<br />

SYMMETRY<br />

The frequency output signal is independent <strong>of</strong> the direction <strong>of</strong> flow (absolute amount <strong>of</strong><br />

the measured variable). The VALUE F LOW m and VALUE F HIGH n must have the<br />

same sign (+ or -). The VALUE F HIGHo (e.g. backflow) corresponds to the mirrored<br />

VALUE F HIGH n (e.g. flow).<br />

125<br />

100<br />

Freq.<br />

➂<br />

0<br />

➀<br />

➁<br />

Q<br />

A0001280<br />

! Note!<br />

• The direction <strong>of</strong> flow can be output via the configurable relay or status outputs.<br />

• SYMMETRY cannot be selected unless the values in the VALUE F LOW (4204) and<br />

VALUE F HIGH (4205) functions have the same sign or one <strong>of</strong> the values is zero. If the<br />

values have different signs, SYMMETRY cannot be selected and an<br />

“ASSIGNMENT NOT POSSIBLE” message is displayed.<br />

(continued on next page)<br />

Issue/Rev. 0.2 (12/12) MN0M023 • Page 79