7 Block OUTPUTS<br />
Function description<br />
OUTPUTS CURRENT OUTPUT (1...3) CONFIGURATION<br />
MEASURING MODE<br />
(continued)<br />
• PULSATING FLOW<br />
If flow is characterized by severe fluctuations as is the case, for example, with<br />
reciprocating pumps, flow components outside the measuring range are buffered,<br />
balanced and output after a maximum delay <strong>of</strong> 60 seconds. If the buffered data cannot<br />
be processed within approx. 60 seconds, a fault/notice message appears.<br />
Under certain plant conditions, flow values can aggregate in the buffer, for example in<br />
the case <strong>of</strong> prolonged and unwanted fluid backflow. However, this buffer is reset in all<br />
relevant programming adjustments which affect the current output.<br />
" Caution!<br />
If the option BATCH UPWARDS or BATCH DOWNWARDS is selected in the function<br />
ASSIGN CURRENT OUTPUT (4000), the option is automatically specified and cannot be<br />
edited.<br />
Detailed explanations and<br />
information<br />
How the current output responds under the following postulated<br />
conditions:<br />
1. Defined measuring range (m–n): m and n have the same sign<br />
mA<br />
20<br />
4<br />
0<br />
➀<br />
and the following flow behavior:<br />
Q<br />
➁<br />
Q<br />
A0001248<br />
t<br />
A0001265<br />
•STANDARD<br />
The current output signal is proportional to the measured variable. The flow<br />
components outside the scaled measuring range are not taken into account for signal<br />
output.<br />
mA<br />
• SYMMETRY<br />
The current output signal is independent <strong>of</strong> the direction <strong>of</strong> flow.<br />
mA<br />
t<br />
A0001267<br />
t<br />
A0001268<br />
• PULSATING FLOW<br />
Flow components outside the measuring range are buffered, balanced and output after<br />
a maximum delay <strong>of</strong> 60 seconds.<br />
mA<br />
A<br />
(continued on next page)<br />
S<br />
S=A<br />
t<br />
A0001269<br />