Proline Promass 83E/F/O Description of Device Functions - FMC ...
Proline Promass 83E/F/O Description of Device Functions - FMC ...
Proline Promass 83E/F/O Description of Device Functions - FMC ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4 Block QUICK SETUP <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />
Function description<br />
QUICK SETUP<br />
QUICK SETUP<br />
BATCHING/DOSING<br />
(1005)<br />
! Note!<br />
This function is only available when the optional s<strong>of</strong>tware package BATCHING is<br />
installed.<br />
Use this function to start the (optional) application specific Setup menu for batching.<br />
Options:<br />
YES<br />
NO<br />
Factory setting:<br />
NO<br />
! Note!<br />
You will find a flowchart <strong>of</strong> the BATCHING setup menu on page 32. For more<br />
information on Setup menus, please refer to the Operating Instructions<br />
<strong>Proline</strong> <strong>Promass</strong> 83, BA 059D/06/en.<br />
T-DAT SAVE/LOAD<br />
(1009)<br />
Use this function to save the parameter settings / configuration <strong>of</strong> the transmitter in a<br />
transmitter DAT (T-DAT), or to load the parameter settings from the T-DAT into the<br />
EEPROM (manual safety function).<br />
Application examples:<br />
• After commissioning, the current measuring point parameters can be saved to the<br />
T-DAT as a backup.<br />
• If the transmitter is replaced for some reason, the data from the T-DAT can be loaded<br />
into the new transmitter (EEPROM).<br />
Options:<br />
CANCEL<br />
SAVE (from EEPROM to T-DAT)<br />
LOAD (from the T-DAT into EEPROM)<br />
Factory setting:<br />
CANCEL<br />
! Note!<br />
• If the target device has an older s<strong>of</strong>tware version, the message “TRANSM. SW–DAT”<br />
is displayed during startup. Then only the “SAVE” function is available.<br />
• LOAD<br />
This function is only possible if the target device has the same s<strong>of</strong>tware version as, or a<br />
more recent s<strong>of</strong>tware version than, the source device.<br />
•SAVE<br />
This function is always available.<br />
Page 26 • MN0M023<br />
Issue/Rev. 0.2 (12/12)