10.2.6 Function group INFORMATION<br />
SPECIAL FUNCTION H BATCHING FUNCTION HCA CONFIGURATION 720<br />
<br />
VALVE PARAMETER 722<br />
<br />
SUPERVISION 724<br />
<br />
OPERATION 726<br />
<br />
INFORMATION 728<br />
Function description<br />
SPECIAL FUNCTION BATCHING FUNCTION INFORMATION<br />
INTERNAL SWITCH<br />
POINT<br />
VALVE 1<br />
(7280)<br />
Use this function to display the internal switch point <strong>of</strong> valve 1 (see function CLOSE<br />
VALVE 1 (7221) on page 153). The value displayed takes the fixed correction quantity<br />
and / or the calculated after run quantity into account.<br />
Display:<br />
max. 7-digit floating-point number [unit]<br />
! Note!<br />
The appropriate unit is taken from the function group SYSTEM UNITS (ACA),<br />
(see page 17).<br />
DRIP QUANTITY<br />
(7281)<br />
Displays the after run calculated (averaged) internally. The value displayed can be<br />
overwritten in this function and the after run can thus be adjusted. The after run quantity<br />
is used to optimize the internal switch point <strong>of</strong> valve 1.<br />
User input:<br />
0...quantity [unit]<br />
! Note!<br />
The after run, entered in this function, is only used for the first batching process. For the<br />
second and following batching processes, the internally calculated after run will be used<br />
again.<br />
The appropriate unit is taken from the function group SYSTEM UNITS (ACA),<br />
(see page 17).<br />
Factory setting:<br />
0 [unit]<br />
VALVE<br />
1 CLOSING TIME<br />
(7282)<br />
Use this function to display the valve closing time calculated internally.<br />
Display:<br />
max. 7-digit floating-point number [ms]<br />
! Note!<br />
• The valve closing time is the period between the switch point <strong>of</strong> valve 1 and the first<br />
undershooting <strong>of</strong> the low flow cut <strong>of</strong>f.<br />
• The data can only be taken as a general trend.<br />