10 Block SPECIAL FUNCTION <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

10.2.6 Function group INFORMATION<br />

SPECIAL FUNCTION H BATCHING FUNCTION HCA CONFIGURATION 720<br />

<br />

VALVE PARAMETER 722<br />

<br />

SUPERVISION 724<br />

<br />

OPERATION 726<br />

<br />

INFORMATION 728<br />

Function description<br />

SPECIAL FUNCTION BATCHING FUNCTION INFORMATION<br />

INTERNAL SWITCH<br />

POINT<br />

VALVE 1<br />

(7280)<br />

Use this function to display the internal switch point <strong>of</strong> valve 1 (see function CLOSE<br />

VALVE 1 (7221) on page 153). The value displayed takes the fixed correction quantity<br />

and / or the calculated after run quantity into account.<br />

Display:<br />

max. 7-digit floating-point number [unit]<br />

! Note!<br />

The appropriate unit is taken from the function group SYSTEM UNITS (ACA),<br />

(see page 17).<br />

DRIP QUANTITY<br />

(7281)<br />

Displays the after run calculated (averaged) internally. The value displayed can be<br />

overwritten in this function and the after run can thus be adjusted. The after run quantity<br />

is used to optimize the internal switch point <strong>of</strong> valve 1.<br />

User input:<br />

0...quantity [unit]<br />

! Note!<br />

The after run, entered in this function, is only used for the first batching process. For the<br />

second and following batching processes, the internally calculated after run will be used<br />

again.<br />

The appropriate unit is taken from the function group SYSTEM UNITS (ACA),<br />

(see page 17).<br />

Factory setting:<br />

0 [unit]<br />

VALVE<br />

1 CLOSING TIME<br />

(7282)<br />

Use this function to display the valve closing time calculated internally.<br />

Display:<br />

max. 7-digit floating-point number [ms]<br />

! Note!<br />

• The valve closing time is the period between the switch point <strong>of</strong> valve 1 and the first<br />

undershooting <strong>of</strong> the low flow cut <strong>of</strong>f.<br />

• The data can only be taken as a general trend.<br />

Page 164 • MN0M023<br />

Issue/Rev. 0.2 (12/12)