10 Block SPECIAL FUNCTION<br />
Function description<br />
SPECIAL FUNCTION BATCHING FUNCTION SUPERVISION<br />
MIN. BATCHING<br />
QUANTITY<br />
(7241)<br />
Use this function to specify a minimum batching quantity. A message is generated if the<br />
minimum batching quantity was not achieved by the time batching ends (e.g. if after run<br />
mode is active). The quantity value is entered as a % or as an absolute value, depending<br />
on the option in the function INPUT FORMAT (7209).<br />
Application:<br />
Message stating that underbatching is present (e.g. the contents <strong>of</strong> the containers does<br />
not correspond to the quantity declared).<br />
User input:<br />
0 to max. value or 0 to 100% (related to the batch quantity)<br />
Factory setting:<br />
0 [unit] (= deactivated)<br />
" Caution!<br />
• When the batching quantity is adjusted (reduced/increased), (see function BATCH<br />
QUANTITY (7203) on page 148), there is no automatic adjustment, i.e. this value<br />
must be determined again and reentered (see also the fault message # 472 in the<br />
Operating Instructions <strong>Proline</strong> <strong>Promass</strong> 83, BA 059D/06/en, Troubleshooting<br />
Chapter).<br />
• Batching (START) is not possible when the fault message is active!<br />
! Note!<br />
• The function is not active if you enter 0 (factory setting).<br />
• As a factory setting, this function is assigned a fault message. This appears for<br />
60 seconds. The fault message can be acknowledged earlier by changing a batching<br />
function.<br />
• If this function is intended more for general monitoring purposes or if there is a short<br />
time lapse between two batching processes, it is advisable to assign this function to a<br />
notice message, (see function ERROR CATEGORY on page 181). However, while the<br />
notice message is active (60 seconds) the next batching can be started and the notice<br />
message is acknowledged.<br />
• This function can be output via the switch output.<br />