Proline Promass 83E/F/O Description of Device Functions - FMC ...
Proline Promass 83E/F/O Description of Device Functions - FMC ...
Proline Promass 83E/F/O Description of Device Functions - FMC ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
10 Block SPECIAL FUNCTION <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />
Function description<br />
SPECIAL FUNCTION BATCHING FUNCTION CONFIGURATION<br />
BATCH STAGES<br />
(7208)<br />
Use this function to define the number <strong>of</strong> batching stages. Batching can be carried out in<br />
several stages, e.g. 2-stage batching with fast and precise batching.<br />
Options:<br />
1-stage (1 valve or 1-stage batching)<br />
2-stage (2 valves or 2-stage batching)<br />
Factory setting:<br />
1-stage (1 valve or 1-stage batching)<br />
! Note!<br />
• The batching stage selection (number <strong>of</strong> valves) is directly dependent on the<br />
configuration <strong>of</strong> the outputs. For 2-stage batching two relay outputs must be available<br />
in the measuring device.<br />
• The functions available in the function group VALVE PARAMETER (page 153) are<br />
dependent on the number <strong>of</strong> batching stages (number <strong>of</strong> valves) selected in this<br />
function.<br />
INPUT FORMAT<br />
(7209)<br />
Use this function to define the entry format <strong>of</strong> the quantities for the switch points <strong>of</strong> the<br />
valves.<br />
Options:<br />
VALUE-INPUT (e.g. 10 [unit])<br />
%-INPUT (e.g. 80 [%])<br />
Factory setting:<br />
VALUE-INPUT<br />
! Note!<br />
The entry format selected in this function is also used in the function groups VALVE<br />
PARAMETER (page 153) and SUPERVISION (page 158).<br />
Page 152 • MN0M023<br />
Issue/Rev. 0.2 (12/12)