<strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />
3 Block MEASURED VARIABLES<br />
Function description<br />
MEASURED VARIABLES MEASURING VALUES ADDITIONAL VALUES<br />
% CARRIER VOLUME<br />
FLOW<br />
(0028)<br />
! Note!<br />
This function is not available unless one <strong>of</strong> the following was selected:<br />
• in the function DENSITY FUNCTION (7000), see page 141:<br />
– % MASS / % VOLUME<br />
– FLEXIBLE and in the function MODE (7010), see page 144, the selection %<br />
VOLUME 2D or % VOLUME 3D<br />
Use this function to display the currently measured volume flow <strong>of</strong> the carrier fluid as a %<br />
(<strong>of</strong> the overall mass flow). Carrier fluid = transporting liquid (e.g. water).<br />
Display:<br />
5-digit floating-point number, including unit and sign<br />
CORRECTED CARRIER<br />
VOLUME FLOW<br />
(0029)<br />
! Note!<br />
This function is not available unless % MASS / % VOLUME was selected in the DENSITY<br />
FUNCTION function (7000), (see page 141).<br />
Use this function to display the currently measured corrected volume flow <strong>of</strong> the carrier<br />
fluid. Carrier fluid = transporting liquid (e.g. water).<br />
Display:<br />
5-digit floating-point number, including unit and sign<br />
% BLACK LIQUOR<br />
(0030) ! Note!<br />
This function is not available unless %-BLACK LIQUOR was selected in the DENSITY<br />
FUNCTION function (7000), (see page 141).<br />
The concentration in %-BLACK LIQUOR is displayed.<br />
Display:<br />
5-digit floating-point number, incl. units<br />
°BAUME<br />
(0031) ! Note!<br />
This function is not available unless °BAUME was selected in the DENSITY FUNCTION<br />
function (7000), (see page 141).<br />
The concentration in °BAUME is displayed.<br />
Display:<br />
5-digit floating-point number, incl. units<br />
°API<br />
(0033) ! Note!<br />
This function is not available unless °API was selected in the DENSITY FUNCTION<br />
function (7000), (see page 141).<br />
The concentration in °API is displayed.<br />
Display:<br />
5-digit floating-point number, incl. units<br />
Issue/Rev. 0.2 (12/12) MN0M023 • Page 15