9 Block BASIC FUNCTION<br />
9.3 Group SYSTEM PARAMETER<br />
9.3.1 Function group CONFIGURATION<br />
BASIC FUNCTION G HART GAA<br />
<br />
PROCESS PARAMETER GIA<br />
<br />
SYSTEM PARAMETER GLA CONFIGURATION 660<br />
Function description<br />
BASIC FUNCTION SYSTEM PARAMETER CONFIGURATION<br />
INSTALLATION<br />
DIRECTION SENSOR<br />
(6600)<br />
Use this function to reverse the sign <strong>of</strong> the flow direction, if necessary.<br />
! Note!<br />
Ascertain the actual direction <strong>of</strong> fluid flow with reference to the direction indicated by<br />
the arrow on the sensor (nameplate).<br />
Options:<br />
NORMAL (flow as indicated by the arrow)<br />
INVERSE (flow opposite to direction indicated by the arrow)<br />
Factory setting:<br />
NORMAL<br />
DENSITY DAMPING<br />
(6602)<br />
The density filter allows the sensitivity <strong>of</strong> the density measuring signal to be lowered with<br />
respect to variations in the density <strong>of</strong> the fluid, e.g. with inhomogeneous liquids. The<br />
damping acts on all functions and outputs <strong>of</strong> the measuring device.<br />
User input:<br />
max. 5-digit number, including unit: 0.00...100.00 s<br />
Factory setting:<br />
0.00 s<br />
FLOW DAMPING<br />
(6603)<br />
Setting the filter depth <strong>of</strong> the digital filter. The sensitivity <strong>of</strong> the flow measurement signal<br />
can be reduced with respect to interference peaks (e.g. in the event <strong>of</strong> a high solid<br />
content, gas bubbles in the fluid etc.). The reaction time <strong>of</strong> the measuring device<br />
increases with every increase in the filter setting. The damping acts on all functions and<br />
outputs <strong>of</strong> the measuring device.<br />
User input:<br />
0...100 s<br />
Factory setting:<br />
Liquid: 0,00 s<br />
Gas: 0,25 s<br />
POSITIVE ZERO RETURN<br />
(6605)<br />
Use this function to interrupt evaluation <strong>of</strong> measured variables. This is necessary when a<br />
piping system is being cleaned, for example.<br />
This setting acts on all function and outputs <strong>of</strong> the measuring device.<br />
Options:<br />
OFF<br />
ON (signal output is set to the “ZERO FLOW” value, temperature and density are still<br />
output)<br />
Factory setting:<br />
OFF<br />
Issue/Rev. 0.2 (12/12) MN0M023 • Page 133