<strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

9 Block BASIC FUNCTION<br />

9.2.2 Function group EPD PARAMETER<br />

BASIC FUNCTION G HART GAA<br />

<br />

PROCESS PARAMETER GIA CONFIGURATION 640<br />

<br />

EPD PARAMETER 642<br />

Function description<br />

BASIC FUNCTION PROCESS PARAMETER EPD PARAMETER<br />

EMPTY PIPE DETECTION<br />

(6420)<br />

Use this function to activate the empty pipe detection (EPD). With empty measuring<br />

tubes the density <strong>of</strong> the fluid falls below the value specified in the function EPD VALUE<br />

LOW.<br />

Options:<br />

OFF<br />

ON<br />

Factory setting:<br />

Liquid: ON<br />

Gas: OFF<br />

" Caution!<br />

• Select a correspondingly low EPD response value in the function EPD VALUE LOW, so<br />

that the difference to the effective density <strong>of</strong> the fluid is sufficiently large enough. This<br />

ensures that totally empty measuring tubes and not partially filled ones are detected.<br />

• For gas measurement we strongly recommend to switch <strong>of</strong>f empty pipe detection.<br />

EPD VALUE LOW<br />

(6423) ! Note!<br />

This function is not available unless the ON selection was selected in the EMPTY PIPE<br />

DETECTION function.<br />

Use this function to set a lower threshold for the measured density value, in order to<br />

detect possible problems in the process indicated by too low density.<br />

User input:<br />

5-digit floating-point number<br />

Factory setting:<br />

0.2000 kg/l<br />

EPD VALUE HIGH<br />

(6424) ! Note!<br />

This function is not available unless the ON selection was selected in the EMPTY PIPE<br />

DETECTION function.<br />

Use this function to set an upper threshold for the measured density value.<br />

User input:<br />

5-digit floating-point number<br />

Factory setting:<br />

6.0000 kg/l<br />

EPD RESPONSE TIME<br />

(6425)<br />

Use this function to enter the time span for which the criteria for an empty pipe have to<br />

be satisfied without interruption before a notice message or fault message is generated.<br />

User input:<br />

fixed-point number: 1.0...100 s<br />

Factory setting:<br />

1.0 s<br />

Issue/Rev. 0.2 (12/12) MN0M023 • Page 125