9 Block BASIC FUNCTION <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />
9.1 Group HART<br />
9.1.1 Function group CONFIGURATION<br />
BASIC FUNCTION G HART GAA CONFIGURATION 600<br />
Function description<br />
BASIC FUNCTION HART CONFIGURATION<br />
TAG NAME<br />
(6000)<br />
Use this function to enter a tag name for the measuring device. You can edit and read this<br />
tag description via the local display or the HART protocol.<br />
User input:<br />
max. 8-character text, permissible: A-Z, 0-9, +, –, punctuation marks<br />
Factory setting:<br />
“_ _ _ _ _ _ _ _” (no text)<br />
TAG DESCRIPTION<br />
(6001)<br />
Use this function to enter a tag description for the measuring device. You can edit and<br />
read this tag description via the local display or the HART protocol.<br />
User input:<br />
max. 16-character text, permissible: A-Z, 0-9, +, –, punctuation marks<br />
Factory setting:<br />
“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (No text)<br />
BUS ADDRESS<br />
(6002)<br />
Use this function to define the address for the exchange <strong>of</strong> data with the HART protocol.<br />
User input:<br />
0...15<br />
Factory setting:<br />
0<br />
! Note!<br />
Addresses 1...15: a constant 4 mA current is applied.<br />
HART PROTOCOL<br />
(6003)<br />
Use this function to display if the HART protocol is active.<br />
Display:<br />
OFF = HART protocol not active<br />
ON = HART protocol active<br />
! Note!<br />
The HART protocol can be activated with the selection 4-20 mA HART or<br />
4-20 mA (25 mA) HART in the function CURRENT SPAN, (see page 64).<br />
WRITE PROTECTION<br />
(6004)<br />
Use this function to check whether the measuring device can be write-accessed.<br />
Display:<br />
OFF = Data exchange is possible<br />
ON = Data exchange disabled<br />
Factory setting:<br />
OFF<br />
! Note!<br />
Write protection is activated and deactivated by means <strong>of</strong> a jumper on the I/O module<br />
(see Operating Instruction <strong>Proline</strong> <strong>Promass</strong> 83, BA 059D/06/en).<br />
Page 120 • MN0M023<br />