17.01.2015 Views

Proline Promass 83E/F/O Description of Device Functions - FMC ...

Proline Promass 83E/F/O Description of Device Functions - FMC ...

Proline Promass 83E/F/O Description of Device Functions - FMC ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

8 Block INPUTS <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

8.1 Group STATUS INPUT<br />

8.1.1 Function group CONFIGURATION<br />

INPUTS F STATUS INPUT FAA CONFIGURATION 500<br />

Function description<br />

INPUTS STATUS INPUT CONFIGURATION<br />

ASSIGN STATUS INPUT<br />

(5000)<br />

Use this function to assign a switching function to the status input.<br />

Options:<br />

OFF<br />

RESET TOTALIZER 1<br />

RESET TOTALIZER 2<br />

RESET TOTALIZER 3<br />

RESET ALL TOTALIZERS<br />

POSITIVE ZERO RETURN<br />

RESET FAULT MESSAGE<br />

ZEROPOINT ADJUSTMENT<br />

Advanced options with optional s<strong>of</strong>tware package BATCHING:<br />

RUN BATCHING (start/stop)<br />

HOLD BATCHING (stop/continue)<br />

RESET BATCH SUM (resetting total quantity / total quantity totalizers)<br />

RESET TOTALIZER 3 & START BATCHING (reset <strong>of</strong> totalizer 3, followed by start)<br />

" Caution!<br />

If an input pulse is sent during a batching process, the batching process is canceled<br />

immediately, but totalizer 3 is not reset. This allows the partial filling to be read out<br />

correctly.<br />

Advanced options with optional s<strong>of</strong>tware package ADVANCED DIAGNOSIS:<br />

ACQUISITION<br />

! Note!<br />

This function is not available unless the SINGLE SHOT setting is selected in the<br />

ACQUISITION MODE function (7410).<br />

Factory setting: OFF<br />

" Caution!<br />

POSITIVE ZERO RETURN is active as long as the level is available at the status input<br />

(continuous signal). All other assignments react to a change in level (pulse) at the status<br />

input.<br />

ACTIVE LEVEL<br />

(5001)<br />

Use this function to define whether the assigned function (see function ASSIGN STATUS<br />

INPUT) is released when the signal level is present (HIGH) or not present (LOW).<br />

Options:<br />

HIGH<br />

LOW<br />

Factory setting: HIGH<br />

MINIMUM<br />

PULSE WIDTH<br />

(5002)<br />

Use this function to define a minimum pulse width which the input pulse must achieve in<br />

order to trigger the selected switching function, (see function ASSIGN STATUS INPUT<br />

(5000)).<br />

User input:<br />

20...100 ms<br />

Factory setting: 50 ms<br />

Page 112 • MN0M023<br />

Issue/Rev. 0.2 (12/12)