<strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

7 Block OUTPUTS<br />

7.3.2 Function group OPERATION<br />

OUTPUTS E CURRENT OUTPUT 1 EAA<br />

<br />

CURRENT OUTPUT 2 EAB<br />

<br />

CURRENT OUTPUT 3 EAC<br />

<br />

PULSE/FREQ. OUTPUT 1 ECA<br />

<br />

PULSE/FREQ. OUTPUT 2 ECB<br />

<br />

RELAY OUTPUT 1 EGA CONFIGURATION 470<br />

<br />

OPERATION 474<br />

RELAY OUTPUT 2 EGB CONFIGURATION 470<br />

<br />

OPERATION 474<br />

Function description<br />

OUTPUTS RELAY OUTPUT (1...2) OPERATION<br />

ACTUAL STATUS RELAY<br />

OUTPUT<br />

(4740)<br />

Use this function to check the current status <strong>of</strong> the relay output.<br />

A jumper on the contact side defines the relay output as a normally open (NO or make) or<br />

normally closed (NC or break) contact (see Operating Instruction <strong>Proline</strong> <strong>Promass</strong> 83, BA<br />

059D/06/en).<br />

Display:<br />

MAKE CONTACT OPEN<br />

MAKE CONTACT CLOSED<br />

BREAK CONTACT OPEN<br />

BREAK CONTACT CLOSED<br />

SIMULATION SWITCH<br />

POINT<br />

(4741)<br />

Use this function to activate simulation <strong>of</strong> the relay output.<br />

Options:<br />

OFF<br />

ON<br />

Factory setting:<br />

OFF<br />

! Note!<br />

• The “SIMULATION RELAY” message indicates that simulation is active.<br />

• The measuring device continues to measure while simulation is in progress, i.e. the<br />

current measured values are output correctly via the other outputs.<br />

• If the “BATCH VALVE 1” option was selected in the ASSIGN RELAY (4700) function,<br />

the functional test takes place by means <strong>of</strong> the BATCH PROCEDURE (7260) function,<br />

see p. 162.<br />

" Caution!<br />

The setting is not saved if the power supply fails.<br />

Issue/Rev. 0.2 (12/12) MN0M023 • Page 105