7 Block OUTPUTS <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />

Function description<br />

OUTPUTS RELAY OUTPUT (1...2) CONFIGURATION<br />

MEASURING MODE<br />

(4705) ! Note!<br />

This function is not visible unless a limit value was assigned to the relay output.<br />

Use this function to define the measuring mode for the relay output.<br />

Options:<br />

STANDARD<br />

The relay output signal switches at the defined switch points.<br />

SYMMETRY<br />

The relay output signal switches at the defined switch points, irrespective <strong>of</strong> the sign. If<br />

you define a switch point with a positive sign, the relay output switches as soon as the<br />

value is reached in the negative direction (negative sign), (see illustration).<br />

Factory setting:<br />

STANDARD<br />

Example for the SYMMETRY measuring mode:<br />

Switch-on point Q = 4<br />

Switch-<strong>of</strong>f point Q = 10<br />

m = Relay energized<br />

n = Relay de-energized<br />

Q<br />

10<br />

4<br />

0<br />

-4<br />

t<br />

-10<br />

➀ ➁ ➀ ➁ ➀<br />

A0001247<br />

! Note!<br />

• SYMMETRY cannot be selected unless the values in the ON VALUE (4701) and OFF-<br />

VALUE (4703) functions have the same sign or one <strong>of</strong> the values is zero.<br />

• If the values have different signs, SYMMETRY cannot be selected and an<br />

“ASSIGNMENT NOT POSSIBLE” message is displayed.<br />

TIME CONSTANT<br />

(4706)<br />

Use this function to enter a time constant defining how the measuring signal reacts to<br />

severely fluctuating measured variables, either very quickly (enter a low time constant) or<br />

with damping (enter a high time constant).<br />

Damping acts on the measuring signal before the switch status changes, and<br />

consequently before switch-on or switch-<strong>of</strong>f delay is activated.<br />

The purpose <strong>of</strong> damping, therefore, is to prevent the relay output changing state<br />

continuously in response to fluctuations in flow.<br />

User input:<br />

fixed-point number: 0.00...100.00 s<br />

Factory setting:<br />

0.00 s<br />