7 Block OUTPUTS <strong>Device</strong> <strong>Functions</strong> <strong>Proline</strong> <strong>Promass</strong> 83<br />
Function description<br />
OUTPUTS RELAY OUTPUT (1...2) CONFIGURATION<br />
MEASURING MODE<br />
(4705) ! Note!<br />
This function is not visible unless a limit value was assigned to the relay output.<br />
Use this function to define the measuring mode for the relay output.<br />
Options:<br />
STANDARD<br />
The relay output signal switches at the defined switch points.<br />
SYMMETRY<br />
The relay output signal switches at the defined switch points, irrespective <strong>of</strong> the sign. If<br />
you define a switch point with a positive sign, the relay output switches as soon as the<br />
value is reached in the negative direction (negative sign), (see illustration).<br />
Factory setting:<br />
STANDARD<br />
Example for the SYMMETRY measuring mode:<br />
Switch-on point Q = 4<br />
Switch-<strong>of</strong>f point Q = 10<br />
m = Relay energized<br />
n = Relay de-energized<br />
Q<br />
10<br />
4<br />
0<br />
-4<br />
t<br />
-10<br />
➀ ➁ ➀ ➁ ➀<br />
A0001247<br />
! Note!<br />
• SYMMETRY cannot be selected unless the values in the ON VALUE (4701) and OFF-<br />
VALUE (4703) functions have the same sign or one <strong>of</strong> the values is zero.<br />
• If the values have different signs, SYMMETRY cannot be selected and an<br />
“ASSIGNMENT NOT POSSIBLE” message is displayed.<br />
TIME CONSTANT<br />
(4706)<br />
Use this function to enter a time constant defining how the measuring signal reacts to<br />
severely fluctuating measured variables, either very quickly (enter a low time constant) or<br />
with damping (enter a high time constant).<br />
Damping acts on the measuring signal before the switch status changes, and<br />
consequently before switch-on or switch-<strong>of</strong>f delay is activated.<br />
The purpose <strong>of</strong> damping, therefore, is to prevent the relay output changing state<br />
continuously in response to fluctuations in flow.<br />
User input:<br />
fixed-point number: 0.00...100.00 s<br />
Factory setting:<br />
0.00 s<br />