QuickSpecs - Alsys Data
QuickSpecs - Alsys Data
QuickSpecs - Alsys Data
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>QuickSpecs</strong><br />
HP ProLiant ML370 Generation 3 (G3)<br />
Power Specifications<br />
Part Number 216068-001<br />
Spare Kit 230993-B21<br />
Operational Input Voltage<br />
90 to 264<br />
Range (V rms)<br />
Frequency Range (Nominal)<br />
47 to 63 (50/60)<br />
(Hz)<br />
Nominal Input Voltage (Vrms) 100 115 208 220 230 240<br />
Max Rated Output Wattage Rating 500 500 500 500 500 500<br />
Nominal Input Current (A rms) 8.1 6.9 3.8 3.5 3.4 3.2<br />
Max Rated Input Wattage Rating (Watts) 794 781 769 758 758 758<br />
Max. Rated VA (Volt-Amp) 810 797 785 773 773 773<br />
Efficiency (%) 63 64 65 66 66 66<br />
Power Factor .98 .98 .98 .98 .98 .98<br />
Leakage Current (mA) .30 .35 .63 .67 .70 .73<br />
Maximum Inrush Current (A peak) 25 25 25 25 25 25<br />
Maximum Inrush Current duration (mS) 20 20 20 20 20 20<br />
System Specifications<br />
ProLiant ML370 Generation 3 Fully Configured<br />
Up to 2 Processors, 6 Memory Slots, 8 Hard Drives, 4 PCI Slots, and 2 Hot Plug Power Supplies<br />
Nominal Input Voltage (Vrms) 100 115 208 220 230 240<br />
Fully Loaded System Input Wattage (W) 704 693 682 672 672 672<br />
Fully Loaded System Thermal (BTU-Hr) 2399 2362 2325 2290 2290 2290<br />
System Leakage with all power supplies loaded (mA) 0.61 0.70 1.27 1.34 1.40 1.46<br />
System Inrush Current with all power supplies loaded (A) 50 50 50 50 50 50<br />
Power cord requirements<br />
Nema 5-15P to IEC320-C13 Option no./Spare no.: See Chart below<br />
IEC320-C13 to IEC320-C14 Option no./Spare no.: 142257-002/142258-B21<br />
NOTES:<br />
* - To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool located at URL:<br />
http://h30099.www3.hp.com/configurator/powercalcs.asp<br />
NOTE: This Web site is available in English only.<br />
To drill down to calculators:<br />
- Click on: "ProLiant Servers"<br />
- Click on the Server of interest. Example: ML370 G3<br />
- Click on: "Power Calculator" link. (You may need to scroll down to see it)<br />
DA - 11450 Worldwide — Version 24 — August 14, 2003 Page 43