Troubleshooting Guide (Continued)<br />
PROBLEM POSSIBLE CAUSE SOLUTION<br />
The low fire flame is weak or<br />
unstable<br />
• Low fire adjusted too low<br />
• Not enough gas<br />
Increase low fire gas setting<br />
Check start-up settings and<br />
adjust to increase low gas flow<br />
The burner goes off when it<br />
cycles to high fire<br />
• Not enough air<br />
• Insufficient air<br />
(flame too rich)<br />
Check sart-up settings.<br />
Investigate any change, i.e.<br />
blocked filter, loose connections<br />
Check start-up settings<br />
Check air filter, clean or<br />
replace if required<br />
The burner is erratic and<br />
does not respond to<br />
adjustment<br />
The burner is unstable or<br />
produces soot or smoke<br />
Cannot achieve full capacity<br />
• Flame signal weak<br />
• Internal damage to the<br />
burner. Some parts<br />
inside the burner my be<br />
loose or dirty<br />
• The air/gas ratio is out of<br />
adjustment<br />
• Air filter is blocked<br />
• Gas pressure is too low into<br />
the main gas pressure regulator<br />
Check condition of flame<br />
monitoring device<br />
Contact your <strong>Eclipse</strong><br />
representative or the <strong>Eclipse</strong><br />
factory<br />
Measure all the gas pressures<br />
and air pressures.<br />
Compare to initial start-up<br />
settings, and adjust them where<br />
necessary<br />
Clean or replace the air filter<br />
Adjust gas pressure<br />
• Increased furnace/chamber<br />
pressures<br />
• Poor piping practices<br />
Re-check setup pressures<br />
Contact factory<br />
32 <strong>Eclipse</strong> <strong>ThermJet</strong> v2, Installation Guide No. 205, 3/5/07