Eclipse ThermJet Burners - Power Equipment Company
Eclipse ThermJet Burners - Power Equipment Company
Eclipse ThermJet Burners - Power Equipment Company
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Yearly Checklist<br />
1.<br />
2.<br />
3.<br />
4.<br />
5.<br />
6.<br />
7.<br />
8.<br />
9.<br />
10.<br />
Inspect flame-sensing devices for good condition and cleanliness.<br />
Check for proper inlet air/gas ratios.<br />
Test all the alarm systems for proper signals.<br />
Check ignition spark plugs and check proper gap.<br />
Check valve motors and control valves for free, smooth action<br />
and adjustment.<br />
Check for proper operation of the ventilating equipment.<br />
Test the interlock sequence of all safety equipment; manually<br />
make each interlock fail, noting that related equipment<br />
closes or stops as specified by the manufacturer.<br />
Test flame monitoring control system by manually shutting<br />
off gas to burner.<br />
Test main fuel hand-valves for operation.<br />
Clean or replace the combustion air blower filter.<br />
<strong>Eclipse</strong> <strong>ThermJet</strong> v2, Installation Guide No. 205, 3/5/07<br />
29