EGW1-MB User’s Manual<br />
<strong>Exemys</strong><br />
<br />
Master Mode<br />
40002-40003 Serial, Requests Count<br />
40004-40005 Serial, Parity Errors<br />
40006-40007 Serial, CRC/LRC Errors<br />
40008-40009 Serial, Length Errors<br />
40010-40011 Serial, Other Errors<br />
40012-40013 Serial, IO's Requests<br />
40014-40015 Serial, IO's exceptions<br />
40016-40017 Serial, Rejected Broadcasts<br />
40018-40019 Serial, Wrong Unit Requests<br />
40020-40021 Serial, Other exceptions<br />
40022-40023 TCP, Socket Openings<br />
40024-40025 TCP, Failed Socket Openings<br />
40026-40027 TCP, Opened Sockets<br />
40028-40029 TCP, Unexpected Closings<br />
40030-40031 TCP, Inactity Time Out Closes<br />
40032-40033 TCP, Valid Responses<br />
40034-40035 TCP, Invalid Headers<br />
40036-40037 TCP, Responses Timed Out<br />
To clear the statistics write on Holding Register 40001 a value different to zero.<br />