EGW1-MB User’s Manual<br />
<strong>Exemys</strong><br />
<br />
<br />
Enter the Message timeout value desired<br />
Click on the “Send” button to make the EGW1-MB take the changes.<br />
From the command console, you must execute the MSGTOUT command.<br />
Table 15 - MSGTOUT command<br />
Command<br />
MSGTOUT:(..)<br />
Description<br />
Changes the maximum waiting period for answer<br />
from the slave. It is expreEGW1-MB d in<br />
milliseconds.<br />
3.2.8.3 Slave Address (Slave Mode)<br />
The field Unit ID of a Modbus/TCP message is conceived to direct multiple slaves to a same IP<br />
address. Some old applications presume the existence of an only Slave for each IP address and<br />
always send the ID field in 0.<br />
EGW1-MB in Slave Mode can be configured to translate all messages from any Unit ID into a<br />
fixed determined address. This option may or may not be enabled, and, also, you may configure<br />
the fixed address to which you wish the messages to be translated. Please note that enabling this<br />
option means a restriction to an only serial slave. To enable or disable this option, or to change<br />
the fixed address from the configuration Web Page:<br />
• Select “Modbus TCP” from the menu<br />
• Enter the fixed Slave address and check the box to enable the option<br />
• Click the “Send” command to make the EGW1-MB take the changes.<br />
From the command console, you may execute the SLVADDR command.<br />
Table 16 - SLVADDR command<br />
Command<br />
SLVADDR:(D|1..255)<br />
Description<br />
Enables/Disables or changes the fixed address to which the<br />
Mode Slave ID address will be translated.<br />
D = Disabled<br />
(1..255) = Enabled/Fixed Address<br />
www.exemys.com Rev. 4 Page27