3.2 Operation<br />
3.2.1 Introduction<br />
EGW1-MB translates the Modbus/TCP messages received from remote masters into<br />
Modbus/ASCII-RTU messages to serial local slaves (Slave Mode), or translates the Modbus/ASCII-<br />
RTU messages from serial local master into Modbus/TCP to remote slaves (Master Mode). Slave<br />
mode can handle up to 8 Modbus/TCP masters, which messages will be translated into<br />
Modbus/ASCII-RTU to local serial slaves (Slave Mode with Multiple Masters).<br />
Slave<br />
Msg:Adress<br />
Msg:ID<br />
Master<br />
Modbus / ASCII - RTU<br />
Modbus TCP<br />
Slave<br />
(A) Master Mode<br />
Slave<br />
Slave<br />
Msg:ID<br />
Msg:Adress<br />
Master<br />
Modbus / TCP<br />
Modbus / ASCII - RTU<br />
Slave<br />
(B) Slave Mode<br />
Slave<br />
Master<br />
Slave<br />
Msg:ID<br />
Msg:Adress<br />
Master<br />
Modbus / TCP<br />
Modbus / ASCII - RTU<br />
Slave<br />
Master<br />
(C) Slave Mode Multimaster<br />
Figure 9 - Master, Slave and Slave-Multimaster modes<br />
Slave<br />
3.2.1.1 Slave Mode.<br />
EGW1-MB Slave Mode translates the Modbus/TCP messages from remote masters into serial local<br />
slaves Modbus/ASCII or Modbus/RTU.<br />
In general, the Unit ID of the Modbus/TCP messages will be directly translated to the addresses of<br />
the serial local slaves, but a fixed Address may also be configured. In models with more than one<br />
serial port EGW1-MB will search the Unit ID in a list to decide which serial port to use with that<br />
message.<br />
3.2.1.2 Master Mode.<br />
EGW1-MB Master mode translates the messages from serial local master Modbus/ASCII or<br />
Modbus/RTU to remote Modbus/TCP slaves.<br />
www.exemys.com Rev. 4 Page16