3.4. ARTIFICIAL VENTILATION<br />

20<br />

Operator’s <strong>Manual</strong><br />

For drive powers above 15 kW natural ventilation is not sufficient. Under certain circumstances this can also apply for smaller power<br />

ratings, e.g.:<br />

-- when locating the compressor in small rooms,<br />

-- if ventilation openings cannot be large enough,<br />

-- when other systems with high heat radiation are operating in the same room or<br />

-- when two or more compressors are operating in the same room.<br />

The principle is: forced ventilation is obligatory if room temperature exceeds the allowed ambient temperature<br />

(45° C)<br />

Cooling air flow<br />

The necessary cooling air flow is calculated to an appoximate value by using the following formula:<br />

Required minimum cooling air volume [m 3 /h] = 360 x drive power [kW]<br />

For calculation of the cooling air duct cross section the following formula can be used:<br />

Cooling air duct [m2 ] = cooling air volume [m3 /h]<br />

cooling air flow [m/s] x 3600 [s/h]<br />

The recommended cooling air flow is approx. 3 to 5 m/s, but max. 10 m/s.<br />

Example: Verticus III, drive power 11 kW:<br />

Cooling air volume = 360 x 11 = 3960 m 3 /h<br />

Cross section =<br />

Methods<br />

3960 m3 /h<br />

3 m/s x 3600 s/h<br />

=0.36m 2<br />

There are several types of artificial ventilation:<br />

-- free air flow effected by a blower<br />

-- ventilation by means of an air channel with or without additional blowera) -- ventilation by means of an air circulating flap with or without additional blowera) If installed correctly, the free air flow cooling method should be sufficient for all VERTICUS compressor units.<br />

a) ATTENTION: Ensure that the max. counter -pressure in the intake and outlet channels Δ p = 0.5 mbar = 5 mm W.G. (measured at a distance<br />

of 1 m from the compressor unit) is not exceeded.