Factory Wiring Diagram<br />
<strong>RS</strong> <strong>70</strong>/M - <strong>RS</strong> 100/M - <strong>RS</strong> 130/M<br />
with burner mounted Siemens LFL control<br />
D2332<br />
Continuous fan operation<br />
Change the wire connection from terminal 6 to terminal 1, move the jumper from terminals 12-13 to terminals 4-12 and<br />
remove the wire from terminal 13 of control box as indicated below.<br />
(A)<br />
LAYOUT (A)<br />
Burner <strong>RS</strong> <strong>70</strong>-100-130/M<br />
• Models <strong>RS</strong> <strong>70</strong>-100-130/M leave the factory preset for 208-230 V power supply.<br />
• If 460 V power supply is used, change the motor connection from delta to star and change the setting of the thermal cut-out as well.<br />
Key to Layout (A)<br />
CMV - Motor contactor<br />
DA - LFL Control box<br />
MB - Burner terminal strip<br />
MV - Fan motor<br />
PA - Air pressure switch<br />
PGM - High gas pressure switch<br />
SM - Servomotor<br />
SO - Ionisation probe (flame rod)<br />
SP - Plug-socket<br />
TA - Ignition transformer<br />
TB - Burner ground<br />
15<br />
D2878