Section 3.3.1 - Proprietary Treatment Systems<br />

• The study must be conducted in the field, as opposed to laboratory testing;<br />

• Field monitoring must be conducted using standard protocols which require proportional<br />

sampling both upstream and downstream <strong>of</strong> the device;<br />

• Concentrations reported in the study must be flow-weighted; and,<br />

• The propriety system or device must have been in place for at least one year at the time <strong>of</strong><br />

monitoring.<br />

Although local data is preferred, data from other regions can be accepted as long as the<br />

design accounts for the local conditions.<br />

3.3.1.3 Other Requirements<br />

• The local jurisdiction may require that the facility be placed in a reserve and/or<br />

establishment <strong>of</strong> a drainage easement the facility, which is accessible from a public road<br />

or other accessible easement. When required, the drainage easement should be at least<br />

20 feet wide, provide a minimum traversable width <strong>of</strong> 15 feet, have a maximum slope <strong>of</strong> no<br />

more than 10%, and be appropriately stabilized to withstand maintenance equipment and<br />

vehicles.<br />

3.3.1.4 Inspection and Maintenance Requirements<br />

Regular inspection and maintenance is critical to the effective operation <strong>of</strong> stormwater<br />

management facilities. An operation and maintenance plan is required and shall include:<br />

1. “Covenants for Permanent Maintenance <strong>of</strong> Stormwater Management Facilities” (also<br />

called the “Maintenance Covenants”). An example covenants document can be found in<br />

<strong>Volume</strong> 3.<br />

2. “Inspection Checklist and Maintenance Guidance” for each type <strong>of</strong> stormwater facility that<br />

is located on the property. Detailed inspection and maintenance guidance must be<br />

prepared by the manufacturer or design engineer.<br />

3. As-built drawings must accurately show the location <strong>of</strong> the facility, and clearly identify<br />

reserves and access easements.<br />

All stormwater management facilities must be maintained in accordance with the O&M Plan.<br />

<strong>Volume</strong> 2, Technical Guidance Page 3 - 149