6 Maintenance<br />

Therefore observe the following EMC rules:<br />

� Choose the earthing option with the lowest possible ohm rate<br />

(e.g. unpainted mounting board of the switching cabinet) for<br />

installation.<br />

� Contact the largest possible surface (skin effect). If necessary,<br />

remove existing paint to achieve large-surface contact.<br />

� From the Central Earthing Point (CEP), lay earthing wires to the<br />

respective connections in a star structure. Earthing circuits are<br />

not admissible and can cause unnecessary distortions.<br />

� Use shielded cables only.<br />

� Only large-surface shield transitions are admissible.<br />

� Shields must not be contacted via pin contacts of connector<br />

plugs.<br />

� By all means observe the switching proposals.<br />

� Cut motor cables to minimum length.<br />

� Do not lay cable circuits inside the switching cabinet.<br />

CAUTION!<br />

Electromagnetic fields!<br />

Disturbances or failure of the system possible!<br />

� With the installation the following rules must be considered, in<br />

order to exclude consequences of excessive disturbance effects<br />

as far as possible.<br />

� In connection with electronic controls, no inductive loads whatsoever<br />

must be switched without suitable interference elimination.<br />

� For DC operation, suitable interference elimination can be<br />

achieved by arranging recovery diodes. For AC operation, commercially<br />

available erasing elements matching the connector<br />

type can be used.<br />

� Only the interference elimination element mounted immediately<br />

at the point of inductivity serves this purpose. In any other case,<br />

the switching pulse may even emit increased interference via the<br />

interference elimination elements. It is much easier to avoid<br />

sources of interference in the first place, than to eliminate the<br />

effects of existing interference.<br />

� In no case must the contacts switching unshielded inductive<br />

loads be arranged in the same room as the MC-4 <strong>Motor</strong>Controller;<br />

the same goes for cables carrying unshielded, switched<br />

inductivity and cables running parallel to them. The control must<br />

be separated from such „distorters“ by a Faraday cage (own<br />

section in the switching cabinet).<br />

page 26 <strong>SB</strong>-<strong>Motor</strong> PacDrive<br />