(ii). Clarification Request #35:<br />

Since the panels will be installed outside and the controller inside, do we have to provide disconnect<br />

switches at the Array and also before the Charge Controller Entry. This means 2 disconnection points<br />

between the PV Array and Charge Controller. Please confirm.<br />

Response:<br />

Refer to the tender specifications for your systems designs for installation. These systems are to be<br />

packaged component stand-alone outside compact systems which are to be installed as complete units<br />

externally from the location being served by each system. All NEC guidelines must be followed as needed<br />

for design. Follow the instructions and you can include changes and/or additions in your design for<br />

evaluation.<br />

(jj). Clarification Request #36:<br />

As per the NEC guidelines, we can isolate one conductor and ground the other conductor or isolate both<br />

current carrying conductors by using appropriate circuit breakers. Please confirm if we can to supply these<br />

isolators / disconnection devices with this tender<br />

Response:<br />

All NEC and SEIAPI technical guidelines must be followed for design of stand-alone system. The guidelines<br />

are available online and have been attached with this email. The tenderer must design the system<br />

following these guidelines.<br />

(kk). Clarification Request #37:<br />

We have a question regarding the mounting structures for the modules.<br />

Will they be rammed into the ground or will there be a concrete foundation<br />

Response:<br />

The systems will be installed on concrete poles. The poles will be prepared by YSPSC but the tenderer<br />

proposal must provide the technical drawings for the poles along with the mounting requirements for the<br />

system/s that they are proposing.<br />

(ll). Clarification Request #38:<br />

Since SCS will be installed outside (compact installation)<br />

please confirm if both the controllers, inverters and all other accessories to be installed outside<br />

Response:<br />

SCS to be outside and please refer to the complete tender dossier and especially the documents of<br />

“Instruction for Tenderers” long with “Annex II” for definition of “PV solar packages” and “complete”<br />

system for both the SCS/SHS. All system components to be included with such.<br />

(mm). Clarification Request #39:<br />

Is SHS also a compact system with controllers and inverters mounted outdoors<br />

Response:<br />

Correct and again please refer to tender document Annex II item “h).” which provides guide to the region<br />

and conditions of the where these systems will be installed. Reference to “<strong>Yap</strong>, Federated <strong>State</strong>s of<br />

Micronesia” is made and which also encompasses the outer islands of the state of <strong>Yap</strong>, FSM. Research and<br />

becoming familiar with this region and the conditions that can be encountered is strongly encouraged.<br />

(nn). Clarification Request #40:<br />

Confirmation on Tender Guarantee<br />

If TG is submitted in another form, say Bank Guarantee or Bank Draft, will the company be disqualified<br />

from the tendering process