Worked Example<br />
Table 1 DC Load (energy) Assessment<br />
(1) (2) (3) (4a) (5a) (4b) (5b) (6) Comments<br />
dry season wet season Contribution<br />
Power<br />
to maximum<br />
Appliance Number<br />
Usage Energy Usage Energy demand<br />
Time<br />
Time<br />
W h Wh h Wh W<br />
Light 4 7 4 112 4 112 28<br />
Daily Load energy-d.c loads (Wh) ( DC 7a) 112 (DC 7b) 112<br />
Maximum d.c. demand (W) (DC 8) 28<br />
Table 2 AC Load (energy) Assessment<br />
(1) (2) (3) (4a) (5a) (4b) (5b) (6) (7) (8) (9a) (9b)<br />
dry season wet season<br />
Contribution<br />
Contribution to<br />
Power<br />
to max<br />
surge demand<br />
Appliance <strong>No</strong>.<br />
Power demand Surge Potential Design<br />
Usage<br />
Time<br />
Energy Usage<br />
Time<br />
Energy Factor<br />
Factor<br />
Comments<br />
W h Wh h Wh VA VA VA<br />
TV 100 3 300 3 300 0.8 125 4 500 125<br />
Refrigerator 100 12 1200 12 1200 0.8 125 4 500 500 Duty cycle of<br />
0.5 included<br />
Daily Load Energy A.C<br />
1500<br />
1500<br />
Loads (Wh) (AC10a)<br />
(AC10b)<br />
maximum demand (VA) (AC11) 250 1000<br />
Surge demand (VA) (AC12) 625<br />
Issue 1 September 2012 Page 3