Led interface<br />

The easy basic interface allows with leds to understand the system operation and the changing internal<br />

state.<br />

In particular the green led monitors the right function of the system during the compensation, and the startup<br />

procedure, lighting in two different way to show the “pre-charge” operation and the “contactor on”<br />

operation.<br />

The four red leds are monitoring the fault that occurs in the filter:<br />

‣ Power supply out of the rated range (“Supply voltage”)<br />

‣ Fault of the contactor or of the inverter section start-up (“Contactor”)<br />

‣ Fault of the internal temperature (“Temperature”)<br />

‣ Fault on the inverter section (“Inverter”)<br />

Active Filter performances<br />

Harmonic pollution: in the following figure there are two waveform of the absorbed current of a typical non<br />

linear load before and after the filtering. In the upper wave a 42 Arms current with THD i of 73% is filtering<br />

and it results the lower wave with 38 Arms and a residual THD i of 8%.<br />

Absorbed current of a non linear load before and after the filtering<br />

10 http://www.comarcond.com