Section 4. Sensor Support<br />

4.7.3 Serial Sensors<br />

4.7.3.1 SDI-12 Sensors<br />

The SDI-12 standard allows cable lengths of up to 200 feet. <strong>Campbell</strong> <strong>Scientific</strong><br />

does not recommend SDI-12 sensor lead lengths greater than 200 feet; however,<br />

longer lead lengths can sometimes be accommodated by increasing the wire<br />

gage and/or powering the sensor with a second 12 vdc power supply placed near<br />

the sensor.<br />