Section 3. Overview<br />

3.1.3.4 Power Terminals<br />

Read More! See <strong>CR200</strong>(X) Power Supply (p. 53).<br />

Power In<br />

• Power Supply: External battery is connected to Battery+ and Batteryterminals.<br />

• Input voltages in excess of 18 V may damage the <strong>CR200</strong> and/or power<br />

supply. Power to charge a 12 V lead-acid battery (16-22 VDC) must be<br />

connected to the Charge+ and Charge- terminals NOT to Battery+ and<br />

Battery-.<br />

Power Out<br />

3.1.3.5 Communications Ports<br />

• Peripheral 12 V Power Source: 1 terminal (SWBattery) and the associated<br />

ground (G) supply power to sensors and peripheral devices requiring<br />

nominal 12 VDC. Sensors and peripheral devices may also share a<br />

connection to the Battery+ and Battery- terminals which is the same as<br />

connecting them directly to the battery. This supply may drop as low as 7<br />

VDC before datalogger operation stops. Precautions should be taken to<br />

minimize the occurrence of invalid data from underpowered sensors.<br />

Read More! See Telecommunications and Data Retrieval (p. 131) and PakBus<br />

Overview (p. 133).<br />

The <strong>CR200</strong>(X) is equipped with an RS-232 communications port. This port<br />

allows the <strong>CR200</strong>(X) to communicate with other computing devices, such as a<br />

PC, or with other <strong>Campbell</strong> <strong>Scientific</strong> dataloggers.<br />

Note RS-232 communications normally operate well up to a transmission cable<br />

capacitance of 2500 picofarads, or approximately 50 feet of commonly available<br />

serial cable.<br />

• 9-pin RS-232: Non-isolated port for communicating with a PC through the<br />

supplied serial cable, serial sensors, or through 3rd party serial<br />

telecommunications devices. Acts as a DTE device with a null-modem<br />

cable.<br />

Read More! See APPENDIX. Serial Port Pin Outs (Appendix p. 21).<br />

Some versions of the <strong>CR200</strong>(X) include an optional spread spectrum radio for<br />

wireless communication with other devices equipped with a spread spectrum<br />

radio.<br />