Section 10. CRBASIC Programming Instructions<br />

While…Wend<br />

Execute a series of statements in a loop as long as a given condition is true.<br />

Syntax<br />

While Condition<br />

[StatementBlock]<br />

Wend<br />

10.5 Measurement Instructions<br />

10.5.1 Diagnostics<br />

Battery<br />

Measures input voltage.<br />

Syntax<br />

Battery (Dest)<br />

10.5.2 Voltage<br />

VoltSe<br />

Measures the voltage at a single-ended input with respect to ground.<br />

Syntax<br />

VoltSe (Dest, Reps, SEChan, Mult, Offset)<br />

Read More! See Bridge Resistance Measurements (p. 41).<br />

ExDelSE<br />

Applies an excitation voltage, delays for a specified period of time, and makes a<br />

single-ended voltage measurement. Allowable excitation voltages are +2500mV<br />

and +5000mV.<br />

Syntax<br />

ExDelSE (Dest, Reps, SEChan, ExChan, ExmV, Delay,<br />

Mult, Offset)<br />

Therm109<br />

Measures a <strong>Campbell</strong> <strong>Scientific</strong> 109 thermistor<br />

Syntax<br />

Therm109 (Dest, Reps, SEChan, Vx/ExChan,<br />

SettlingTime, Integ, Mult, Offset)<br />

10.5.3 Pulse<br />

Read More! See Pulse Count Measurement (p. 42).<br />

Note Pull-up resistors are required when using digital I/O (control) ports for<br />

pulse input (Pulse Input on Digital I/O Channels C1 - C2 (p. 45)).<br />