For <strong>Moeller</strong> Electric Sales and Support call KMparts.com (866) 595-9616<br />

15/58<br />

Technical Data<br />

Radio interference suppression filter<br />

DE51-LZ...<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

DE51-LZ1-<br />

007-V2<br />

DE51-LZ1-012-<br />

V2<br />

DE51-LZ1-<br />

024-V2<br />

DE51-LZ3-<br />

007-V4<br />

DE51-LZ3-<br />

011-V4<br />

DE51-LZ3-020-<br />

V4<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

General<br />

Standards<br />

EN 50178, IEC 61800-3, EN 61800-3 incl. A11<br />

Environmental conditions<br />

Operating temperature °C –25…+100<br />

Altitude m 0…1000 a.s.l., derating above 1000: Ie…2 %/1000 m<br />

Mounting position<br />

As required, vertically suspended preferred<br />

Free surrounding areas<br />

In connection area (cable, terminals): 80 mm<br />

Humidity class<br />

C<br />

Climatic class (IEC) 25/085/21<br />

Protection type<br />

IP 20 (terminals)<br />

Dimensions (W x H x D) mm 80 x 170 x 27 110 x 180 x 35 110 x 180 x 35 110 x 285 x 40<br />

Weight kg 0.45 0.5 0.67 0.7 0.75 1.2<br />

Electrical data<br />

Test voltage in V DC, 2 s<br />

Phase/neutral pole V 1100 1100 1100 2100 2100 2100<br />

Phase/PE V 2550 2550 2550 2650 2650 2650<br />

Leakage current<br />

Max. leakage current in operation mA < 6 < 6 < 6 < 11 < 35 < 46<br />

Max. leakage current when PE<br />

mA < 25 < 26 < 24 < 4 < 5 < 5.5<br />

disconnected<br />

Max. leakage current when PE and N mA < 47 < 51 < 48 – – –<br />

disconnected<br />

Max. leakage current PE and 2 external mA – – – < 156 < 198 < 210<br />

conductors disconnected<br />

Rated operating voltage V AC 230 230 230 400 400 400<br />

Rated voltage U e V 1 AC 250 V 3 AC 480 V<br />

Supply <strong>frequency</strong> Hz 50/60 (47…63 g 0 %)<br />

Rated operational current<br />

U i = 1-phase, 230 V AC I A 7 12 24 – – –<br />

U i = 3-phase, 400 V AC I A – – – 7 11 20<br />

Permissible overcurrent<br />

150 % for 60 s, every 30 minutes<br />

Heat dissipation with rated operational<br />

current I e<br />

W 5 7 12 4 7 12<br />

Terminal capacities<br />

Solid mm 2 0.2…4<br />

flexible mm 2 0.2…4<br />

Cables to <strong>frequency</strong> inverter mm 2 2 x 1.5, 180 mm 2 x 2.5, 250 mm<br />

AWG 18 16 12 18 16 12<br />

PE stud M5 x 15<br />

Notes<br />

All rating data is based on an ambient temperature of +40°C.<br />

I 1.2 B<br />

I 1.0 N<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

0<br />

0<br />

20 40 60 80 100<br />

i[°C]