15/48<br />

Technical Data<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

Technical Data<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

15/49<br />

<strong>DF</strong>6<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

<strong>DF</strong>6<br />

<strong>DF</strong>6-340-45K <strong>DF</strong>6-340-55K <strong>DF</strong>6-340-75K <strong>DF</strong>6-340-90K <strong>DF</strong>6-340-110K <strong>DF</strong>6-340-132K<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

Power loss<br />

at 100 % e W 2300 2800 3800 4800 5500 6650<br />

at 70 % e W 1625 1975 2675 3375 3900 4670<br />

Efficiency % 95.1 95.1 95.2 95.2 95.2 95.2<br />

Dimensions (W x H x D) mm 396 x 556 x 270.5 396 x 556 x 270.5 396 x 556 x 270.5 396 x 706 x 290.5 396 x 706 x 290.5 486 x 746 x 282<br />

Weight kg 30 30 30 60 60 80<br />

Power section<br />

Rated operating voltage V AC 400 400 400 400 400 400<br />

Rated voltage e V 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC<br />

Supply <strong>frequency</strong> Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)<br />

Mains current<br />

i = 3-phase, 400 V AC A 94 116 149 176 215 253<br />

Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760<br />

Modulation method Pulse width modulation (PWM), / -predetermined control Pulse width modulation (PWM), / -predetermined control<br />

Switching <strong>frequency</strong> 5 kHz, can be selected between 0.5 and 12 kHz 5 kHz, can be selected between 0.5 and 8 kHz<br />

Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e<br />

Output <strong>frequency</strong> Hz 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5…50, max. 360 0.5…50, max. 360<br />

<strong>Frequency</strong> resolution Hz 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values<br />

<strong>Frequency</strong> error limit at 20 C g 10 K<br />

g0.01 % of the maximum <strong>frequency</strong> with digital setpoint values, g0.2 % of the maximum <strong>frequency</strong><br />

g0.01 % of the maximum <strong>frequency</strong> with digital setpoint values, g0.2 % of the maximum <strong>frequency</strong> with analog setpoint values<br />

with analog setpoint values<br />

Max. rated operational current e A 85 105 135 160 195 230<br />

Permissible overcurrent 120 % for 60 s/150 % for 0.5 s, every 600 s 120 % for 60 s/150 % for 0.5 s, every 600 s<br />

Torque during start Quadratic, linear load characteristic (base <strong>frequency</strong> 30 – 400 Hz) Quadratic, linear load characteristic (base <strong>frequency</strong> 30 – 400 Hz)<br />

Apparent power at 400 V kVA 58.8 72.7 93.5 111 135 159<br />

Apparent power at 480 V kVA 70.1 87.1 112 133 162 191<br />

Standard operation with 120 % overload. Assigned<br />

motor rating (4-pole ASM)<br />

400 V kW 45 55 75 90 110 132<br />

460 V HP 60 75 100 125 150 175<br />

Brake transistor<br />

Switching threshold DC V DC – – – – – –<br />

Resistor B at 100 % c.d.f. O – – – – – –<br />

Lowest impedance B O – – – – – –<br />

Max. duty factor (c.d.f.) with lowest<br />

% <strong>DF</strong> – – – – – –<br />

impedance B<br />

Control circuit<br />

Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch<br />

Relay<br />

1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive<br />

load/3 A resistive load,2 x make contacts, 230 V AC/1 A inductive load/5 A resistive load or 24 V DC/<br />

1 A inductive load/5 A resistive load<br />

1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive load/3 A resistive load,2 x make contacts, 230 V AC/1 A<br />

inductive load/5 A resistive load or 24 V DC/1 A inductive load/5 A resistive load<br />

Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485<br />

Control voltage<br />

Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA<br />

Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA<br />

Parameterization 2 parameter sets (online/offline parameterization), parameter protection (programmable) 2 parameter sets (online/offline parameterization), parameter protection (programmable)<br />

Inputs<br />

digital (parameters can be defined) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field)<br />

analog, 8 bit resolution Amount 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O) 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O)<br />

Outputs<br />

analog (parameters can be defined), 8 bit resolution 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA<br />

4 – 20 mA (load impedance max. 250 O) 4 – 20 mA (load impedance max. 250 O)<br />

PWM (parameters can be defined) 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA<br />

Terminal capacities<br />

Cable lengths<br />

mm 2 35 50 2 x 35 2 x 35 2 x 50 2 x 70<br />

AWG 1 1/0 2 x 1 2 x 1 2 x 1/0 2 x 1/0<br />

Relay connection<br />

mm 2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5<br />

AWG 26…16 26…16 26…16 26…16 26…16 26…16<br />

Control circuit<br />

mm 2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5<br />

AWG 16… 6 16… 6 16… 6 16… 6 16… 6 16… 6<br />

Notes<br />

If the <strong>frequency</strong> inverter is to be installed in a control panel, enclosure or similar installation, the<br />

prevalent ambient within these enclosuresor control panels is considered to be the ambient<br />

temperature a .<br />

All rating data of the power section are based on a switching <strong>frequency</strong> of 5 kHz (default setting) and<br />

an ambient temperature of +40 °C, with operation of a four pole three-phase asynchronous motor.<br />