06.01.2015 Views

Moeller Frequency inverters DF Vector frequency inverters DV

Moeller Frequency inverters DF Vector frequency inverters DV

Moeller Frequency inverters DF Vector frequency inverters DV

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

For <strong>Moeller</strong> Electric Sales and Support call KMparts.com (866) 595-9616<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

15/46<br />

Technical Data<br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

<strong>DF</strong>6<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Technical Data<br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

<strong>DF</strong>6-340-11K <strong>DF</strong>6-340-15K <strong>DF</strong>6-340-18K5 <strong>DF</strong>6-340-22K <strong>DF</strong>6-340-30K <strong>DF</strong>6-340-37K<br />

Power loss<br />

at 100 % e W 600 800 975 1150 1550 1900<br />

at 70 % e W 435 575 698 820 1100 1345<br />

Efficiency % 94.8 94.8 95 95 95 95.1<br />

Dimensions (W x H x D) mm 216 x 266 x 190.5 216 x 266 x 190.5 256 x 396 x 210.5 256 x 396 x 210.5 256 x 396 x 210.5 316 x 546 x 215.5<br />

Weight kg 5 5 12 12 12 20<br />

Power section<br />

Rated operating voltage V AC 400 400 400 400 400 400<br />

Rated voltage e V 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC<br />

Supply <strong>frequency</strong> Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)<br />

Mains current<br />

i = 3-phase, 400 V AC A 24 32 41 47 63 77<br />

Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760<br />

Modulation method Pulse width modulation (PWM), / -predetermined control Pulse width modulation (PWM), / -predetermined control<br />

Switching <strong>frequency</strong> 5 kHz, can be selected between 0.5 and 12 kHz 5 kHz, can be selected between 0.5 and 12 kHz<br />

Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e<br />

Output <strong>frequency</strong> Hz 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400<br />

<strong>Frequency</strong> resolution Hz 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values<br />

<strong>Frequency</strong> error limit at 20 C g 10 K<br />

g0.01 % of the maximum <strong>frequency</strong> with digital setpoint values, g0.2 % of the maximum <strong>frequency</strong><br />

g0.01 % of the maximum <strong>frequency</strong> with digital setpoint values, g0.2 % of the maximum <strong>frequency</strong> with analog setpoint values<br />

with analog setpoint values<br />

Max. rated operational current e A 22 29 37 43 57 70<br />

Permissible overcurrent 120 % for 60 s/150 % for 0.5 s, every 600 s 120 % for 60 s/150 % for 0.5 s, every 600 s<br />

Torque during start Quadratic, linear load characteristic (base <strong>frequency</strong> 30 – 400 Hz) Quadratic, linear load characteristic (base <strong>frequency</strong> 30 – 400 Hz)<br />

Apparent power at 400 V kVA 15.2 20 25.6 29.7 39.4 48.4<br />

Apparent power at 480 V kVA 18.2 24.1 30 35.7 47.3 58.1<br />

Standard operation with 120 % overload. Assigned<br />

motor rating (4-pole ASM)<br />

400 V kW 11 15 18.5 22 30 37<br />

460 V HP 15 20 25 30 40 50<br />

Brake transistor<br />

Switching threshold DC V DC 740 740 – – – –<br />

Resistor B at 100 % c.d.f. O 150 150 – – – –<br />

Lowest impedance B O 50 50 – – – –<br />

Max. duty factor (c.d.f.) with lowest<br />

% <strong>DF</strong> 10 10 – – – –<br />

impedance B<br />

Control circuit<br />

Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch<br />

Relay<br />

1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive<br />

load/3 A resistive load,2 x make contacts, 230 V AC/1 A inductive load/5 A resistive load or 24 V DC/<br />

1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive load/3 A resistive load,2 x make contacts, 230 V AC/1 A<br />

inductive load/5 A resistive load or 24 V DC/1 A inductive load/5 A resistive load<br />

1 A inductive load/5 A resistive load<br />

Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485<br />

Control voltage<br />

Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA<br />

Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA<br />

Parameterization 2 parameter sets (online/offline parameterization), parameter protection (programmable) 2 parameter sets (online/offline parameterization), parameter protection (programmable)<br />

Inputs<br />

digital (parameters can be defined) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field)<br />

analog, 8 bit resolution Amount 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O) 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O)<br />

Outputs<br />

analog (parameters can be defined), 8 bit<br />

resolution<br />

1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA<br />

4 – 20 mA (load impedance max. 250 O) 4 – 20 mA (load impedance max. 250 O)<br />

PWM (parameters can be defined) 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA<br />

Terminal capacities<br />

Cable lengths<br />

mm 2 6 10 16 25 25 35<br />

AWG 8 6 6 4 3 1<br />

Relay connection<br />

mm 2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5<br />

AWG 26…16 26…16 26…16 26…16 26…16 26…16<br />

Control circuit<br />

mm 2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5<br />

AWG 16… 6 16… 6 16… 6 16… 6 16… 6 16… 6<br />

Notes<br />

If the <strong>frequency</strong> inverter is to be installed in a control panel, enclosure or similar installation, the<br />

prevalent ambient within these enclosuresor control panels is considered to be the ambient<br />

temperature a .<br />

All rating data of the power section are based on a switching <strong>frequency</strong> of 5 kHz (default setting) and<br />

an ambient temperature of +40 °C, with operation of a four pole three-phase asynchronous motor.<br />

<strong>DF</strong>6<br />

15/47<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong>