For <strong>Moeller</strong> Electric Sales and Support call KMparts.com (866) 595-9616<br />

15/42<br />

Technical Data<br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

Technical Data<br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

<strong>DV</strong>51<br />

<strong>DV</strong>51<br />

<strong>DV</strong>51-322-025 <strong>DV</strong>51-322-037 <strong>DV</strong>51-322-055 <strong>DV</strong>51-322-075 <strong>DV</strong>51-322-1K1 <strong>DV</strong>51-322-1K5 <strong>DV</strong>51-322-2K2 <strong>DV</strong>51-320-4K0 <strong>DV</strong>51-320-5K5 <strong>DV</strong>51-320-7K5<br />

General<br />

Heat dissipation with rated operational current I e W 21 26 29 41 55 90 105 0 0 0<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

Dimensions (W H D) mm 80 120 103 80 120 117 80 120 117 110 130 139 110 130 139 110 130 166 110 130 166 110 130 166 180 220 155 180 220 155<br />

Weight kg 0.7 0.85 0.95 1.3 1.3 1.8 1.8 1.8 5.5 5.7<br />

Rated operating voltage V AC 230 230 230 230 230 230 230 230 230 230<br />

Rated voltage e V 1 AC 180…264 V 0 %<br />

1 AC 180…264 V 0 %<br />

3 AC 180…264 V 0 %<br />

3 AC 180…264 V 0 %<br />

3 AC 180…264 V 0 %<br />

Supply <strong>frequency</strong> Hz 50/60 (47…63 0 %) 50/60 (47…63 0 %)<br />

Mains current<br />

i = 230 V AC monoph. A 3.5 5.8 6.7 9 11.2 17.5 24 – – –<br />

i = 230 V AC triph. A 2 3.4 3.9 5.2 6.5 10 14 22 30 40<br />

Alternative DC supply DC V DC 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 %<br />

Modulation method Sensorless vector control, pulse width modulation (PWM) Sensorless vector control, pulse width modulation (PWM)<br />

Switching <strong>frequency</strong> 5 kHz, can be selected between 2 and 14 kHz 5 kHz, can be selected between 2 and 14 kHz<br />

Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e<br />

Output <strong>frequency</strong> Hz 0 to 50, max. 400 0 to 50, max. 400<br />

<strong>Frequency</strong> resolution Hz 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values 0.1, with digital setpoint values/maximum <strong>frequency</strong>/1000 with analog setpoint values<br />

<strong>Frequency</strong> error limit at 20 C 10 K 0.01 % of maximum <strong>frequency</strong> for digital reference values, 0.2 % of maximum <strong>frequency</strong> for<br />

analog reference values<br />

0.01 % of maximum <strong>frequency</strong> for digital reference values, 0.2 % of maximum <strong>frequency</strong> for analog reference values<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

Max. rated operational current e A 1.6 2.6 3 4 5 8 11 17.5 24 32<br />

Permissible overcurrent 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s<br />

Torque during start From 1 Hz: more than 200 % with sensorless vector control From 1 Hz: more than 200 % with sensorless vector control<br />

Apparent power at 240 V kVA 0.6 1 1.2 1.6 2 3.3 4.5 7.2 9.9 13.3<br />

Standard operation at 150 % overload Assigned<br />

motor rating (4-pole ASM)<br />

230 V kW 0.25 0.37 0.55 0.75 1.1 1.5 2.2 4 5.5 7.5<br />

240 V HP 1 1 2 3 5 7.5 10<br />

Brake transistor<br />

Switching threshold DC V DC 380 380 380 380 380 380 380 380 380 380<br />

Lowest impedance B 100 100 100 100 70 70 70 70 70 70<br />

Duty factor % <strong>DF</strong> 40 54 36 53 44 40 36 40 36 36<br />

Relay<br />

1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A<br />

1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A inductive load, 3 A resistive load<br />

inductive load, 3 A resistive load<br />

Serial interface RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485<br />

Control voltage<br />

Output setpoint voltage V +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA<br />

Output control voltage V +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA<br />

Parameterization 2 2<br />

Inputs<br />

digital (parameters can be defined) 6 +24 V DC, configurable 6 +24 V DC, configurable<br />

Analog Inputs Amount 2 0 to +10 V DC (input impedance 10 k , 4 to 20 mA (load impedance 250 ), resolution 10 bit 2 0 to +10 V DC (input impedance 10 k , 4 to 20 mA (load impedance 250 ), resolution 10 bit<br />

Outputs<br />

Digital 2 24 V DC transistor (open-collector, configurable) 2 24 V DC transistor (open-collector, configurable)<br />

analog (parameters can be defined) 1 0 to +10 V DC, 1 mA (configurable), resolution 10 bit 1 0 to +10 V DC, 1 mA (configurable), resolution 10 bit<br />

Cable lengths<br />

Relay connection<br />

Control circuit<br />

mm 2 1.5 1.5 1.5 2.5 2.5 4 4 2.5 4 4<br />

AWG 16 16 16 14 14 12 12 14 12 12<br />

mm 2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5<br />

AWG 6 6 6 6 6 6 6 6 6 6<br />

mm 2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5<br />

AWG 6 6 6 6 6 6 6 6 6 6<br />

If the <strong>frequency</strong> inverter is to be installed in an enclosure, control panel or similar housing, the<br />

ambient temperature a is taken to be the temperature inside this enclosure or control panel.<br />

All rating data of the power section is based on a switching <strong>frequency</strong> of 5 kHz (default setting) and<br />

an ambient temperature of +40 °C, for operation of a four-pole three-phase asynchronous motor.