<strong>Frequency</strong> Inverters – Overview<br />

15/3<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

<strong>DV</strong>51<br />

<strong>Vector</strong> <strong>inverters</strong> <strong>DV</strong>51-320 <strong>DV</strong>51-322 <strong>DV</strong>51-340 <strong>DV</strong>6-340<br />

Rated voltage<br />

230 V AC 230 V AC 400 V AC 400 V AC<br />

(50/60Hz g5%)<br />

1 AC 180…264 V g 0 % – K – –<br />

3 AC 180…264 V g 0 % K K – –<br />

3 AC 342…528 V g 0 % – – K K<br />

Rated operational current 17.5…32 A 1.6…11 A 1.5…16 A 2.8…286 A<br />

Assigned motor rating at rated voltage 4…7.5 kW 0.25…7.5 kW 0,37…7.5 kW 0.75 … 132 kW<br />

PID controller K K K K<br />

Built-in braking chopper (external braking resistance) K K K <strong>DV</strong>6-340-075 …<br />

<strong>DV</strong>6-340-11K<br />

Keypad Option DEX-KEY-6…, DEX-KEY-10 K<br />

Communication interface RS 485, Modbus RTU (optionally PROFIBUS-DP, CANopen) RS 422, RS 485, (optionally<br />

PROFIBUS-DP)<br />

Product standard EN 50178, IEC 61800-3<br />

Approvals CE, UL, c-UL, cTick CE, UL, c-UL,CSA, cTick<br />

Degree of protection<br />

IP20<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

Ambient temperature<br />

Operating temperature °C -10 to +40 with rated current I e at a clock <strong>frequency</strong> of 5 kHz; up to +50 °C at a reduced clock <strong>frequency</strong> of 2 kHz<br />

and reduced output current of 80 % I e .<br />

Storage °C –25…+70<br />

Mechanical shock resistance<br />

Vibration and impact, max. 5.9 m/s 2 (0.6 g) at 10 to 55 Hz<br />

Pollution degree VDE 0110 Part 2, pollution degree 2<br />

Climatic proofing Class 3K3 according to EN 50178 (non-condensing, average relative humidity 20 to 90 %)<br />

Altitude m 0 to 1000 m a.s.l., above 1000 m with reduced current (2.5 %/100 m)<br />

Mounting position<br />

Vertically suspended<br />

Free surrounding areas<br />

100 mm above and below device<br />

Emitted interference IEC/EN 61800-3 (EN 55011 group 1 class B)<br />

Noise immunity<br />

IEC/EN 61800-3, industrial environment<br />

Insulation resistance Overvoltage category III according to VDE 0110<br />

Leakage current to PE mA < 3.5 (to EN 50178)<br />

Contact protection<br />

Finger and back-of-hand proof<br />

Protective isolation from switching<br />

Safe isolation from the mains. Double basic isolation (to EN 50178)<br />

circuitry<br />

Protective measures<br />

Overcurrent, earth fault, overvoltage, undervoltage, overload, overtemperature, electronic overload protection:<br />

I 2 t monitoring and PTC input (thermistor or thermostat)<br />

Notes<br />

If the <strong>frequency</strong> inverter is to be installed in an enclosure, control panel or similar housing, the ambient temperature T a is<br />

taken to be the temperature inside this enclosure or control panel.<br />

All rating data of the power section is based on a switching <strong>frequency</strong> of 5 kHz (default setting) and an ambient temperature<br />

of +40 °C, for operation of a four-pole three-phase asynchronous motor.<br />

For <strong>Moeller</strong> Electric Sales and Support call KMparts.com (866) 595-9616