For <strong>Moeller</strong> Electric Sales and Support call KMparts.com (866) 595-9616<br />

Engineering<br />

Connection example<br />

15/25<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

<strong>DV</strong>6<br />

Block diagram <strong>DV</strong>6<br />

In their default configuration, the <strong>DV</strong>6 vector <strong>frequency</strong> <strong>inverters</strong> can be used at their assigned supply voltage<br />

and motor rating (four-pole, three-phase asynchronous motor) without any parameter changes. Their<br />

acceleration and deceleration times are set to 30 seconds. The control signal inputs and outputs have the<br />

following assigned functions:<br />

+24 V<br />

FWD<br />

REV<br />

FF1<br />

FF2<br />

2CH<br />

FRS<br />

JOG<br />

AT<br />

RST<br />

P24<br />

7 8 FW<br />

1 2 3 4 5 6<br />

RJ 45<br />

RS 422<br />

SN<br />

RS 485<br />

–<br />

+<br />

RP<br />

SN<br />

Terminal 1:<br />

Terminal 2:<br />

Terminal 3:<br />

Terminal 4:<br />

Terminal 5:<br />

RST = Reset<br />

AT = change over to analog input<br />

OI<br />

JOG = inching duty<br />

FRS = free run stop of motor<br />

(controller inhibit)<br />

2CH = Second parameter set<br />

Terminal 6: FF2 = Fixed <strong>frequency</strong> 2<br />

Terminal 7: FF1 = Fixed <strong>frequency</strong> 1<br />

Terminal 8: REV = Anticlockwise rotating field<br />

enable (Reverse)<br />

Terminal FW: FWD = Clockwise rotating field<br />

enable (Forward)<br />

Terminal FM: Output <strong>frequency</strong> (PWM signal)<br />

Terminal AMI: Output <strong>frequency</strong> (analog signal<br />

4...20 mA)<br />

Terminal AM: Output <strong>frequency</strong> (analog signal<br />

0...10 V)<br />

Terminal 11: FA1 = <strong>frequency</strong> reaches set point<br />

Terminal 12: RUN = Running<br />

Terminal 13: OL = overload signal<br />

Terminal 14: QTQ = torque reached (exceeded)<br />

Terminal 15: IP = mains failure; immediate stop<br />

signal<br />

Terminals K11-K12: Relay, fault signal (K11-K14 ready<br />

for operation)<br />

Note:<br />

Terminal BR*: Brake resistor; for <strong>DV</strong>6-320-11K<br />

and <strong>DV</strong>6-340-075K to <strong>DV</strong>6-340-<br />

15K only<br />

Through the built-in keypad, all parameters and<br />

functions can be adapted to the application.<br />

L+<br />

<strong>Frequency</strong> <strong>inverters</strong><br />

<strong>Vector</strong> <strong>frequency</strong> <strong>inverters</strong><br />

DC+<br />

SP<br />

DC–<br />

–<br />

+<br />

BR*<br />

PLC CM1 TH FM AMI AM H O OI L O2<br />

3<br />

L1 L2 L3<br />

RO TO<br />

R Br<br />

PE<br />

J51<br />

CM2<br />

K1<br />

13 14 15<br />

U V W PE K12 K14 K11<br />

11 12<br />

M<br />

3 ~<br />

e<br />

–10 V...+10 V<br />

0 V<br />

4...20 mA<br />

0...10 V<br />

+10 V<br />

0...+10 V<br />

4...20 mA<br />

10 V (PWM)<br />

PTC<br />

IP<br />

QTQ<br />

OL<br />

RUN<br />

FA1<br />

i<br />

P24<br />

+24 V