A1/34<br />
Motor-protective circuit-breakers<br />
Motor-protective circuit-breakers,Circuit-breakers<br />
PKZ2, PKZ2…-CB<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
http://catalog.moeller.net<br />
<strong>Approvals</strong> for world markets<br />
Rating data for approved types 1)<br />
UL 508/CSA C 22.2 No. 14<br />
Maximum motor rating Setting ranges Maximum protective device to UL/CSA<br />
AC<br />
HP = PS<br />
200 V<br />
HP<br />
230 V<br />
HP<br />
460 V<br />
HP<br />
Overload<br />
Releases<br />
575 V<br />
HP A A<br />
shortcircuit<br />
releases<br />
Group protection 1)<br />
up to max.<br />
short-circuit<br />
current<br />
480 V<br />
kA<br />
Maximum<br />
fuse<br />
600 V<br />
kA A A<br />
PKZ2 motor-protective “Manual Motor Starter with thermal <strong>and</strong> magnetic trip”<br />
circuit-breaker<br />
PKZ2/ZM-0,6 2) 0.4 … 0.6 5 … 8 65 42 500 600<br />
PKZ2/ZM-1 ½ ½ 0.6 … 1 8 … 14 65 42 500 600<br />
PKZ2/ZM-1,6 ¾ 1 1 … 1.6 14 … 22 65 42 500 600<br />
PKZ2/ZM-2,4 ½ ½ 1 1½ 1.6 … 2.4 20 … 35 65 42 500 600<br />
PKZ2/ZM-4 1 1 2 3 2.4 … 4 35 … 55 65 42 500 600<br />
PKZ2/ZM-6 1½ 1½ 3 5 4 … 6 50 … 80 65 42 500 600<br />
PKZ2/ZM-10 2 3 5 7½ 6 … 10 80 … 140 65 42 500 600<br />
PKZ2/ZM-16 3 5 10 10 10 … 16 130 … 220 65 42 500 600<br />
PKZ2/ZM-25 7½ 7½ 20 25 16 … 27 200 … 350 65 42 500 600<br />
PKZ2/ZM-32 10 10 20 30 24 … 32 275 … 425 65 42 500 600<br />
PKZ2/ZM-40 10 15 30 30 32 … 42 350 … 500 65 42 500 600<br />
High-capacity<br />
“Manual Motor Starter with thermal, magnetic trip <strong>and</strong> contactor”<br />
compact starter PKZ2<br />
PKZ2/ZM-0,6/S(...) 2) 0.4 … 0.6 5 … 8 65 42 2000 2000<br />
PKZ2/ZM-1/S(...) ½ ½ 0.6 … 1 8 … 14 65 42 2000 2000<br />
PKZ2/ZM-1.6/S(...) ¾ 1 1 … 1.6 14 … 22 65 42 2000 2000<br />
PKZ2/ZM-2,4/S(...) ½ ½ 1 1½ 1.6 … 2.4 20 … 35 65 42 2000 2000<br />
PKZ2/ZM-4/S(...) 1 1 2 3 2.4 … 4 35 … 55 65 42 2000 2000<br />
PKZ2/ZM-6/S(...) 1½ 1½ 3 5 4 … 6 50 … 80 65 42 2000 2000<br />
PKZ2/ZM-10/ 2 3 5 7½ 6 … 10 80 … 140 65 42 2000 2000<br />
PKZ2/ZM-16/S(...) 3 5 10 10 10 … 16 130 … 220 65 42 2000 2000<br />
PKZ2/ZM-25/S(...) 7½ 7½ 20 25 16 … 27 200 … 350 65 42 2000 2000<br />
PKZ2/ZM-32/S(...) 10 10 20 30 24 … 32 275 … 425 65 42 2000 2000<br />
PKZ2/ZM-40/S(...) 10 15 30 30 32 … 42 350 … 500 65 42 2000 2000<br />
High-capacity contact module "Contact module" in combination with PKZ2/ZM(R)-...<br />
motor-protective circuit-breaker or base for separate mounting of EZ-PKZ2<br />
S-PKZ2(...) 10 15 30 30<br />
S/HI20-S-PKZ2(...) 10 15 30 30<br />
S-G-PKZ2(...) 10 15 30 30<br />
Reversing combination "Reversing combination" in combination with ZM-...PKZ2 trip block for motor protection<br />
PKZ2/SW-MV-11(...) 10 15 30 30<br />
Reversing busbar system<br />
42 A 600 V AC<br />
For UL/CSA-conformance, oder a BK50/3-PKZ2 terminal separately.<br />
Maximum<br />
circuitbreaker<br />
1)Attention: Changed requirements for<br />
group protection<br />
2)Calculate motor power in this range<br />
according to the rated current.<br />
Setting range Group protection Part no.<br />
Overload releases Short-circuit releases Short-circuit power Article no.<br />
at 240 V<br />
Price<br />
See Price<br />
List<br />
Std. pack<br />
Notes<br />
I r<br />
I rm<br />
A A kA<br />
PKZ2 circuit-breaker<br />
Rating data for approved types<br />
UL 489<br />
10…16 130…220 10 PKZ2/ZM-16-CB<br />
264044<br />
1 off Service Factor (SF)<br />
Set value Ir on the current scale,<br />
depending on the load factor<br />
SF = 1.15 a I r = 1 x I nmot<br />
SF = 1 a I r =0.9xI nmot