For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616<br />

http://catalog.moeller.net<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Motor-protective circuit-breakers<br />

Type F starter combinations<br />

PKZM0<br />

A1/33<br />

Maximum motor rating<br />

Setting ranges<br />

AC<br />

HP = PS<br />

Overload<br />

Releases<br />

Short-circuit<br />

release<br />

Rated short-circuit breaking<br />

capacity<br />

200 V 230 V 460 V 575 V 240 V 480 V<br />

277 V 2) 600 V<br />

347 V 2) Incoming terminal Motorprotective<br />

circuit-breakers<br />

HP HP HP HP A A kA kA kA<br />

Contactor<br />

1) 0.1 – 0.16 2.2 50 50 50 BK25/3-PKZ0-E PKZM0-0,16 DILEM-... or DILM7-…<br />

0.16 – 0.25 3.4 50 50 50 BK25/3-PKZ0-E PKZM0-0,25 DILEM-... or DILM7-…<br />

0.25 – 0.4 5.6 50 50 50 BK25/3-PKZ0-E PKZM0-0,4 DILEM-... or DILM7-…<br />

<strong>Approvals</strong> for world markets<br />

0.4 – 0.63 8.8 50 50 50 BK25/3-PKZ0-E PKZM0-0,63 DILEM-... or DILM7-…<br />

½ ½ 0.63 – 1 14 50 50 50 BK25/3-PKZ0-E PKZM0-1 DILEM-... or DILM7-…<br />

¾ 1 1 – 1.6 22 50 50 50 BK25/3-PKZ0-E PKZM0-1,6 DILEM-... or DILM7-…<br />

½ ½ 1 1½ 1.6 – 2.5 35 50 50 50 BK25/3-PKZ0-E PKZM0-2,5 DILEM-... or DILM7-…<br />

1 1 2 3 2.5 – 4 56 50 50 50 BK25/3-PKZ0-E PKZM0-4 DILEM-... or DILM7-…<br />

1½ 1½ 3 5 4 – 6.3 88 50 50 50 BK25/3-PKZ0-E PKZM0-6,3 DILEM-... or DILM7-…<br />

3 3 7½ 10 6.3 – 11 140 50 50 50 BK25/3-PKZ0-E PKZM0-10 DILM9-…<br />

3 3 7½ – 9 – 12 168 18 18 – BK25/3-PKZM0-E PKZM0-12 DILM12-…<br />

3 5 10 – 10 – 16 224 18 18 – BK25/3-PKZ0-E PKZM0-16 DILM17-…<br />

5 5 10 – 16 … 20 280 18 18 – BK25/3-PKZ0-E PKZM0-20 DILM25-…<br />

5 7½ 15 – 20 … 25 350 18 18 – BK25/3-PKZ0-E PKZM0-25 DILM25-…<br />

7½ 10 20 – 25 … 32 448 18 18 – BK25/3-PKZ0-E PKZM0-32 DILM32-…<br />

3 5 10 15 10 – 16 224 50 50 50 BK50/3-PKZM4-E PKZM4-16 DILM17-…<br />

5 7½ 15 20 16 … 27 350 50 50 50 BK50/3-PKZM4-E PKZM4-25 DILM25-…<br />

7½ 10 25 30 24 … 34 448 50 50 50 BK50/3-PKZM4-E PKZM4-32 DILM32-…<br />

10 15 30 30 32 … 40 560 50 50 50 BK50/3-PKZM4-E PKZM4-40 DILM40<br />

1) 0.1 – 0.16 2.2 18 18 18 BK25/3-PKZ0-E PKZM0-0,16 SE00-...-PKZ0(...)<br />

0.16 – 0.25 3.4 18 18 18 BK25/3-PKZ0-E PKZM0-0,25 SE00-...-PKZ0(...)<br />

0.25 – 0.4 5.6 18 18 18 BK25/3-PKZ0-E PKZM0-0,4 SE00-...-PKZ0(...)<br />

0.4 – 0.63 8.8 18 18 18 BK25/3-PKZ0-E PKZM0-0,63 SE00-...-PKZ0(...)<br />

½ ½ 0.63 – 1 14 18 18 18 BK25/3-PKZ0-E PKZM0-1 SE00-...-PKZ0(...)<br />

¾ 1 1 – 1.6 22 18 18 18 BK25/3-PKZ0-E PKZM0-1,6 SE00-...-PKZ0(...)<br />

½ ½ 1 1½ 1.6 – 2.5 35 18 18 18 BK25/3-PKZ0-E PKZM0-2,5 SE00-...-PKZ0(...)<br />

1 1 2 3 2.5 – 4 56 18 18 18 BK25/3-PKZ0-E PKZM0-4 SE00-...-PKZ0(...)<br />

1½ 1½ 3 5 4 – 6.3 88 18 18 18 BK25/3-PKZ0-E PKZM0-6,3 SE00-...-PKZ0(...)<br />

3 3 7½ 10 6.3 – 11 140 18 18 18 BK25/3-PKZ0-E PKZM0-10 SE00-...-PKZ0(...)<br />

Notes<br />

Type F starter combinations do not need an upstream protective device. For<br />

use in Canada, the switch must be fitted with an AK-PKZ0.<br />

Service Factor (SF)<br />

Set value I r on the current scale, depending on the load factor<br />

SF = 1.15 l I r = 1 x I n mot<br />

SF = 1 l I r = 0.9 x I n mot<br />

1) Calculate motor power in this range according to the rated current.<br />

Stated values to NEC Table 430 … 150<br />

2) Suitable for networks with earthed star-point