For <strong>Moeller</strong> <strong>Electric</strong> Sales <strong>and</strong> Support call KMparts.com (866) 595-9616<br />
http://catalog.moeller.net<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Motor-protective circuit-breakers<br />
Type F starter combinations<br />
PKZM0<br />
A1/33<br />
Maximum motor rating<br />
Setting ranges<br />
AC<br />
HP = PS<br />
Overload<br />
Releases<br />
Short-circuit<br />
release<br />
Rated short-circuit breaking<br />
capacity<br />
200 V 230 V 460 V 575 V 240 V 480 V<br />
277 V 2) 600 V<br />
347 V 2) Incoming terminal Motorprotective<br />
circuit-breakers<br />
HP HP HP HP A A kA kA kA<br />
Contactor<br />
1) 0.1 – 0.16 2.2 50 50 50 BK25/3-PKZ0-E PKZM0-0,16 DILEM-... or DILM7-…<br />
0.16 – 0.25 3.4 50 50 50 BK25/3-PKZ0-E PKZM0-0,25 DILEM-... or DILM7-…<br />
0.25 – 0.4 5.6 50 50 50 BK25/3-PKZ0-E PKZM0-0,4 DILEM-... or DILM7-…<br />
<strong>Approvals</strong> for world markets<br />
0.4 – 0.63 8.8 50 50 50 BK25/3-PKZ0-E PKZM0-0,63 DILEM-... or DILM7-…<br />
½ ½ 0.63 – 1 14 50 50 50 BK25/3-PKZ0-E PKZM0-1 DILEM-... or DILM7-…<br />
¾ 1 1 – 1.6 22 50 50 50 BK25/3-PKZ0-E PKZM0-1,6 DILEM-... or DILM7-…<br />
½ ½ 1 1½ 1.6 – 2.5 35 50 50 50 BK25/3-PKZ0-E PKZM0-2,5 DILEM-... or DILM7-…<br />
1 1 2 3 2.5 – 4 56 50 50 50 BK25/3-PKZ0-E PKZM0-4 DILEM-... or DILM7-…<br />
1½ 1½ 3 5 4 – 6.3 88 50 50 50 BK25/3-PKZ0-E PKZM0-6,3 DILEM-... or DILM7-…<br />
3 3 7½ 10 6.3 – 11 140 50 50 50 BK25/3-PKZ0-E PKZM0-10 DILM9-…<br />
3 3 7½ – 9 – 12 168 18 18 – BK25/3-PKZM0-E PKZM0-12 DILM12-…<br />
3 5 10 – 10 – 16 224 18 18 – BK25/3-PKZ0-E PKZM0-16 DILM17-…<br />
5 5 10 – 16 … 20 280 18 18 – BK25/3-PKZ0-E PKZM0-20 DILM25-…<br />
5 7½ 15 – 20 … 25 350 18 18 – BK25/3-PKZ0-E PKZM0-25 DILM25-…<br />
7½ 10 20 – 25 … 32 448 18 18 – BK25/3-PKZ0-E PKZM0-32 DILM32-…<br />
3 5 10 15 10 – 16 224 50 50 50 BK50/3-PKZM4-E PKZM4-16 DILM17-…<br />
5 7½ 15 20 16 … 27 350 50 50 50 BK50/3-PKZM4-E PKZM4-25 DILM25-…<br />
7½ 10 25 30 24 … 34 448 50 50 50 BK50/3-PKZM4-E PKZM4-32 DILM32-…<br />
10 15 30 30 32 … 40 560 50 50 50 BK50/3-PKZM4-E PKZM4-40 DILM40<br />
1) 0.1 – 0.16 2.2 18 18 18 BK25/3-PKZ0-E PKZM0-0,16 SE00-...-PKZ0(...)<br />
0.16 – 0.25 3.4 18 18 18 BK25/3-PKZ0-E PKZM0-0,25 SE00-...-PKZ0(...)<br />
0.25 – 0.4 5.6 18 18 18 BK25/3-PKZ0-E PKZM0-0,4 SE00-...-PKZ0(...)<br />
0.4 – 0.63 8.8 18 18 18 BK25/3-PKZ0-E PKZM0-0,63 SE00-...-PKZ0(...)<br />
½ ½ 0.63 – 1 14 18 18 18 BK25/3-PKZ0-E PKZM0-1 SE00-...-PKZ0(...)<br />
¾ 1 1 – 1.6 22 18 18 18 BK25/3-PKZ0-E PKZM0-1,6 SE00-...-PKZ0(...)<br />
½ ½ 1 1½ 1.6 – 2.5 35 18 18 18 BK25/3-PKZ0-E PKZM0-2,5 SE00-...-PKZ0(...)<br />
1 1 2 3 2.5 – 4 56 18 18 18 BK25/3-PKZ0-E PKZM0-4 SE00-...-PKZ0(...)<br />
1½ 1½ 3 5 4 – 6.3 88 18 18 18 BK25/3-PKZ0-E PKZM0-6,3 SE00-...-PKZ0(...)<br />
3 3 7½ 10 6.3 – 11 140 18 18 18 BK25/3-PKZ0-E PKZM0-10 SE00-...-PKZ0(...)<br />
Notes<br />
Type F starter combinations do not need an upstream protective device. For<br />
use in Canada, the switch must be fitted with an AK-PKZ0.<br />
Service Factor (SF)<br />
Set value I r on the current scale, depending on the load factor<br />
SF = 1.15 l I r = 1 x I n mot<br />
SF = 1 l I r = 0.9 x I n mot<br />
1) Calculate motor power in this range according to the rated current.<br />
Stated values to NEC Table 430 … 150<br />
2) Suitable for networks with earthed star-point